Loading...
HomeMy WebLinkAboutCAG2019-220 - Change Order - #2 - Scarsella Bros, Inc - 228th St UPRR Grade Separation Bridge & Roadway - 12/23/2019 Agreement Routing Form • For Approvals,Signatures and Records Management This form combines&replaces the Request for Mayor's Signature and Contract Cover Sheet forms. K E N T WASHINGTON (Print on pink or cherry colored paper) Originator: Department: S. Anderson PW Engineering Date Sent: Date Required: > 2/24/20 N/A 0 aAuthorized to Sign: Date of Council Approval: Q I7 Director or Designee ❑ Mayor N/A Budget Account Number: Grant? 0 Yes ❑ No Budget? ElYes ❑No Type: Federal,State,Local Vendor Name: Category: Scarsella Bros, Inc. Contract Vendor Number: Sub-Category: C 34547 Change Order 0 Project Name S.228th St. Union Pacific Railroad Grade Separation Bridge and Roadway Phase 5 0 Add the following specification section 8-31 Use Geofoam material of min.EPS 22 can be used at the limits shown on plan sheet 28 for bid C Project Details.item 12150. EPS 22 is acceptable from subgrade to load distribution stab. E Agreement Amount: $41,400 Basis for Selection of Contractor: Bid 4) i Start Date: N/A Termination Date: N/A a Local Business? ❑Yes O No* *If meets requirements per KCC 3.70.700,please complete"Vendor Purchase-Local Exceptions"form on Cityspoce. Notice required prior to disclosure? Contract Number: U"' — �0 ❑Yes I]No CI 12 0 ICI �21 2 T Date Received by City Attorney: Comments: G1 C 3 3 0 cc a N •� L Cps Date Routed to the Mayor's Office: Vf Date Routed to the City Clerk's Office: adaW22373_1_20 Visit Documents.KentWA.gov to obtain copies of all agreements • KENT W A 5 H i N G T 0 1 CHANGE ORDER NO. # 2 NAME OF CONTRACTOR: Scarsella Bros, Inc. ("Contractor") CONTRACT NAME & PROJECT NUMBER:S. 228th St. Union Pacific Railroad Grade Separation Bridge and Roadway Phase 5 ORIGINAL CONTRACT DATE: April 19, 2019 This Change Order amends the above-referenced contract; all other provisions of the contract that are not inconsistent with this Change Order shall remain in effect. For valuable consideration and by mutual consent of the parties, the project contract is modified as follows: 1. Section I of the Agreement, entitled "Description of Work," is hereby modified to add additional work or revise existing work as follows: In addition to work required under the original Agreement and any prior Amendments, Contractor shall provide all labor, materials, and equipment necessary to: This change makes the following revision to the contract documents: Add the following specification section 8-33: Used Geofoam material of min. EPS 22 can be used at the limits shown on plan sheet 28 for bid item 12150. EPS 22 is acceptable from subgrade to load distribution slab. 2. The contract amount and time for performance provisions of Section II "Time of Completion," and Section III, "Compensation," are hereby modified as follows: Original Contract Sum, $13,802,146.40 (including applicable alternates and WSST) Net Change by Previous Change Orders $4,680.00 (incl. applicable WSST) Current Contract Amount $13,806,826.40 (incl. Previous Change Orders) Current Change Order $41,400.00 Applicable WSST Tax on this Change $0.00 Order Revised Contract Sum $13,765,426.40 CHANGE ORDER - 1 OF 3 Original Time for Completion 240 working days (insert date) Revised Time for Completion under 240 working days prior Change Orders (insert date) Days Required (f) for this Change Order calendar days Revised Time for Completion 240 working days (insert date) In accordance with Sections 1-04.4 and 1-04.5 of the Kent and WSDOT Standard Specifications, and Section VII of the Agreement, the Contractor accepts all requirements of this Change Order by signing below. Also, pursuant to the above-referenced contract, Contractor agrees to waive any protest it may have regarding this Change Order and acknowledges and accepts that this Change Order constitutes final settlement of all claims of any kind or nature arising from or connected with any work either covered or affected by this Change Order, including, without limitation, claims related to contract time, contract acceleration, onsite or home office overhead, or lost profits. This Change Order, unless otherwise provided, does not relieve the Contractor from strict compliance with the guarantee and warranty provisions of the original contract, particularly those pertaining to substantial completion date. All acts consistent with the authority of the Agreement, previous Change Orders (if any), and this Change Order, prior to the effective date of this Change Order, are hereby ratified and affirmed, and the terms of the Agreement, previous Change Orders (if any), and this Change Order shall be deemed to have applied. The parties whose names appear below swear under penalty of perjury that they are authorized to enter into this contract modification, which is binding on the parties of this contract. 3. The Contractor will adjust the amount of its performance bond (if any) for this project to be consistent with the revised contract sum shown in section 2, above. IN WITNESS, the parties below have executed this Agreement, which will become effective on the last date written below. CONTRACTOR: CITY OF KENT: By: '� By: � t (signature) C-gA:O 0ZECEAJ (signature) Print Name: W,4TT2s157,1 (.RARdz2GA Print Name: Timothy J. LaPorte, P.E. Its ,�.Gorf�i wAlvyli4dFL l�s' y Public Works Director (title) (title) DATE: DATE: CHANGE ORDER - 2 OF 3 ATTEST: APPROVED AS TO FORM: (applicable if Mayor's signature required) !'.rn vv1 Kent City Clerk Kent Law Department [In this field,you may enter the electronic filepath where the contract has been saved] CHANGE ORDER - 3 OF 3 • FILE NO: 200.2 KENT CHANGE ORDER WORKSHEET NO. 002 Construction Management Division - Public Works Project S. 228th St Union Pacific Railroad Project No.: 07-3022 Grade Separation Ph 5 Project Engineer: Cameron Bloomer, PE Fed-Aid No.: HLP 1216 (006) Owners Rep: KBA, Inc Contractor: Scarsella Bros. Inc. Date: 11/8/2019 I. PROPOSED CHANGE This Change makes the following revisions to the Contract Documents: • Add the following to Specification Section 8-33: Used Geofoam material of min. EPS 22 can be used at the limits shown on plan sheet 28 for bid item 12150. EPS 22 is acceptable from subgrade to load distribution slab. II. REASON AND BACKGROUND FOR CHANGE The Contractor proposed a credit to substitute used geofoam in place of the specified new material under the interurban trail. The City, after confirming suitability of the used material, accepted the proposal to reduce project cost and carbon footprint. III. METHOD OF PAYMENT NEW PAY ITEM(S) ❑ Not Applicable Change Order No. - FOR ACCOUNTING USE ONLY Sch. No. Item Description Total Est. Qty this Unit Unit Price Total Estimated Cost of Qty PE Item .... ......... ... ........... ... ......... ......... ............. ............ ........ ............. .... ............ ............. Used Geofoam - Trail 230 . .... ......... ......... .......... ..... ..... ......... ......... ❑ Independent Estimate Attached ❑ CREATE PAY ITEM ONLY — Payment to be made ❑ PAY THIS PAY ESTIMATE - REQUIRED at a later date upon completion of work ......... ......... ...... ....... ........................ ............ ................ ❑ Material Submittals Reauired — CC: Construction Coordinator New Sub Reqrd? No DELETE EXISTING PAY ITEM(S) per 1-09.5 ❑ Not Applicable Change Order No. - FOR ACCOUNTING USE ONLY Sch. No. B.I. No. Item Description Qty Unit Unit Price Cost of Item ....._._ .. ......._....... _... ........ ........... 12 12150 Geofoam -2300 CY $95.00 -$218,500 ........ .... ......_... .... .... . ............ ..... ........ .... ❑ Independent Estimate Attached - REQUIRED ❑ INCREASE/DECREASE TO EXISTING PAY ITEM(S) ® Not Applicable Change Order No. - FOR ACCOUNTING USE ONLY Sch. No. B.I. No. Item Description Qty Unit Unit Price Cost of Item 1 REV. DATE: 3/15/19 • FILE NO: 200.2 KENT Wa=� ��,o� _............. ............................................................._......_...........................................................................................................__.._._....................................._...................__._._..........._i......_..........._...__........_......................._......_..._............_............_............ Independent Estimate Attached -REQUIRED TOTAL ESTIMATED COST OF CHANGE ORDER * —$41,400 *Total of the Cost of Item Columns THIS PAY ESTIMATE 0 IV. WORKING DAYS Original Contract 240 Due This Change Order* 0 Previous Total 240 ......._ .... . ......... ............. .. .. ._..—...._.................. . ............ ... .._..._........_..............._._...._._......_..._._...._............................... DATE ......... .... ............. ........................... .................................. DATE: . �.._.._..._............_.. ............................. ............_.............. * : Explanation/Justification Required: Material substitution does not impact the time for completion and no additional days are being added via this change order. TOTAL WORKING DAYS* 240 *This Change Order + Previous Total All work, materials and measurements to be in accordance with the Standard Specifications and Contract Special Provisions for the type of work described. Prepared By: Cameron Bloomer Date: 11/8/19 Construction Supervisor: f� ' PA Xate: Z �3 i Construction Manager: �'�j'"'� ' �112�` Date: T 2 REV. DATE: 3/15/19 �.o October 8,2019 City of Kent 220 Fourth Avenue South Kent,WA 98032 Attn: Cameron Bloomer Field Engineer KBA, Inc. RE: 07-3022 228th St. UPRR Phase 5 Reused Geofoam for Interurban Trail SCARSELLA BROS. IS PLEASED TO SUBMIT THE FOLLOWING CHANGE ORDER PROPOSAL FOR THIS PROJECT. ITEM DESCRIPTION UNIT QUANTITY UNIT PRICE BID AMOUNT NEW Geofoam-Reused Material CY 2,300 $ 77.00 S 177,100.00 12150 Geofoam CY 2,300 $ 95.00 $ 218,500.00 TOTAL $ (41,400.00) NOTES: 1. Assume 2,300 CY of reused geofoam taken from WSDOT Contract#9160 Alaskan Way Viaduct Replacement. Reused geofoam proposed for Interurban Trail embankment. 2. Trim and installation procedure to follow if Change Order Proposal is acceptable. Sincerely, Matthew Scarsella Project Manager Barry, Jason From: Cameron Bloomer <cbloomer@kbacm.com> Sent: Wednesday, October 09, 2019 6:30 AM To: Madfai, Mark; Connor, Eric Cc: Smith, Susanne Provencio; Barry, Jason; Kuehne, Paul Subject: Fwd: 228th Ph 5 - COP 007 Reused Geofoam for Interurban Trail Attachments: COP 007 Reused Geofoam for Interurban Trail_Revl.pdf; ATT00001.htm EXTERNAL EMAIL Hello Mark/Eric, Attached is a revised proposal to substitute used Geofoam for new as fill under the trail, bumping the credit up to—$41k. They would cut the used foam into clean pieces prior to use on the project. Please review, I can bring the clean cut sample pieces back in anytime. Thanks, Cameron Bloomer 206.819.7148 Begin forwarded message: From: Matthew Scarsella <matthew.s@SCARSELLABROS.com> Date: October 8, 2019 at 3:29:49 PM PDT To: Cameron Bloomer<cbloomer@kbacm.com> Cc: "JBarry@kentwa.gov" <JBarrV@kentwa.gov>, Nick Venema <nick.v@SCARSELLABROS.com> Subject: COP 007 Reused Geofoam for Interurban Trail Cameron, Please find attached a revised Change Order Proposal for the reuse of geofoam for the Interurban Trail. Thanks, Matt Scarsella Bros., Inc. Matthew Scarsella, P.E. I Project Manager P.O. Box 68697 Seattle, Washington 98168-0697 o: (253) 872-7173 1 c: (206) 817-2765 matthew.s@scarsellabros.com 1 s August 9,2019 City of Kent 220 Fourth Avenue South Kent,WA 98032 Attn: Cameron Bloomer Field Engineer KBA, Inc. RE: 07-3022 228th St. UPRR Phase 5 Reused Geofoam for Interurban Trail SCARSELLA BROS. IS PLEASED TO SUBMIT THE FOLLOW I C OR/PROPOSAL ROJECT: ITEM DESCRIPTION U QUANTITY UNIT PRICE BID AMOUNT NEW Geofoam-Reused Material 2,300 $ 83.00 $ 190,900.00 12150 Geofoam CY 2,300 $ 95.00 $ 218,500.00 TOT $ (27,600.00) NOTES: 1. Assu/stallation, reused geofoam taken from WSDOT Contract#9160 Alaskan Way Viaduct Replacement. Reusoposed for Interurban Trail embankment. 2. Trim procedure to follow if Change Order Proposal is acceptable. Sincerely, Matthew Scarsella Project Manager Gravel Borrow for Structural Earth Wall ........................9-03.14(4) Construction Geosynthetic .........................................9-33 8-33.2(1) Geofoam Geofoam shall be expanded polystyrene (EPS) blocks conforming to ASTM D6817 and shall meet the requirements of Table 8-33.1: Table 8-33.1 TYPE - ASTM ASTM EPS15 EPS19 EPS22 EPS29 EPS39 EPS46 D6817 Density, min., C303 14.4 18.4 21.6 28.8 38.4 45.7 kg/m3(lb/ft) (0.90) (1.15) (1.35) (1.80) (2.40) (2.85) Compressive D1621 25 40 50 75 103 128 Resistance @ 1% (3.6) (5.8) (7.3) (10.9) (15.0) (18.6) deformation, min., kPa (psi) Flexural Strength C 203 172 207 276 345 414 517 min., kPa (psi) (25.0) (30.0) (40.0) (50.0) (60.0) (75.0) Oxygen Index, C2863 24.0 24.0 24.0 24.0 24.0 24.0 min., Volume Geofoam blocks shall be treated by the manufacturer with a tested and proven termite treatment used for below grade applications, 3 year minimum field exposure. The treatment shall be EPA registered, meet requirements of ICC ES AC239, and be recognized in a UL or ICC ES report. Geofoam blocks shall contain a flame-retardant additive and shall have Underwriters Laboratories, Inc. (UL) Certification of Classification as to External Fire Exposure and Surface Burning Characteristics. Manufacturer shall have a UL classification in category BRYX. Geofoam may be manufactured using material with recycled content provided the physical properties of Table 1 are met. If recycled EPS material is used, its use shall be clearly stated by the molder or primary molder in each Manufacturer's Certification of Compliance and the source of the recycled EPS (block-molded versus shape-molded EPS, in-plant versus post-consumer) shall be stated clearly. 8-33.2(1) Geomembrane Geomembrane shall be a reinforced or unreinforced tri-polymer membrane manufactured from polyvinyl chloride (PVC), ethylene interpolymer alloy and polyurethane, or a comparable polymer combination. Geomembrane must confine spilled liquid hydrocarbons, 228`h UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 40 March 22, 2019 Project Number: 07-3022 including gasoline, diesel fuel, kerosene, hydraulic fluid, methanol, ethanol, mineral spirits, and naptha. Geomembrane shall be flexible and, by its own weight, shall conform to 90-degree edges and corners of EPS blocks at 450F ambient temperatures, without applying additional heating of the geomembrane heat. Geomembrane shall meet the requirements of Table 8-33.2 Table 8-33.2 Geomembrane Physical Property ASTM Designation Acceptance Value Unleaded Gasoline D 814 0.4 oz./ft2 Maximum Permeability per 24 hours Thickness D 7512 28 mils Minimum Grab Tensile Strength D 7512 550 Ibf Minimum each (1" grip, 4" x 8" direction sample) Elongation at break D 46322 20 percent min Toughness (Percent N/A 14,000 Ibf Minimum Elongation x Grab Tensile Strength) Puncture Resistance D 7513 800 Ibf Minimum (ball tip) Cold Crack Resistance D 21382 Pass at -30OF (1" mandrel, 4 hours) Factory Produced D 7514 1.25" Minimum Seams, Bonded Width Factory Produced D 7514 320 Ibf Minimum Seams, Shear Strength Field Produced Seams, D 5641 Pass Vapor Tight Seal 'Specified as Minimum or Maximum, not average roll properties. 2Or ASTM test method appropriate for specific polymer. 3Or FTMS 101C, Method 2065. 4Modified per NSF Standard No. 54. 8-33.3 Construction Requirements 8-33.3(1) Submittals and Quality Assurance The Contractor shall submit the following: A. (Type 1 Working Drawings) Geofoam manufacturer's product literature and technical data sheets, including: 1. Manufacturer's recommendations for care, protection, and 228`h UPRR Bridge &Roadway Ph 5/Smith & Madfai 8 - 41 March 22, 2019 Project Number: 07-3022 handling of geofoam blocks. 2. ICC-ES or UL Evaluation report with ASTM D6817 recognition for each Type specified. 3. Product certificate showing evidence of UL Classification QORW Third Party Quality Control for ASTM D6817. Product certificates that only include ASTM C578 recognition are not equivalent and will be rejected. 4. 10-year physical property warranty. B. (Type 2 Working Drawing) Field construction manual for geofoam. C. (Type 2 Working Drawing) Technical data and test data for geofoam block connectors. D. At least 30 calendar days prior to the start of work requiring the geofoam blocks, Type 2 Working Drawings of geofoam block layout and details. At least the following shall be included: 1. Geofoam installation narrative, including construction sequence along South 228th Street driveways and interurban trail, during embankment and retaining wall backfill construction and, as applicable, staged construction. 2. Plan views, elevations, and sections of block layout as appropriate for the installation, showing geometry and identifying type, size and type of geofoam, orientation of geofoam blocks. 3. Sections and details of the geosynthetic layers behind the geofoam, including dimensions such as layer heights, construction geotextile materials, backfill materials. 4. Joint locations and details for staged construction where applicable. 5. Details for accommodating penetrations such as pipes and conduit and infill of voids around pipes and conduits. 6. Block-to-block connection details, including location and details of adhesive and connectors plates at horizontal joints between layers of blocks. 7. Connection details for shotcrete facing, including means for supporting the welded wire fabric reinforcement. 8. Details for geomembrane. 9. Methods and details for assuring stability of the geofoam during placement, including construction of shotcrete facing. This includes, but is not limited to, ballasting or guying techniques, block-to-block connections involving connectors and/or adhesive. 10. Methods for protection of geofoam during construction, including, but not limited to, protection against vehicle traffic traversing over the geofoam and adjacent to geofoam embankments. 228" UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 42 March 22, 2019 Project Number: 07-3022 11. Field cutting and repair procedures and equipment. 12. Methods of geofoam protection against moisture, sunlight, and wind. 13. Description, size, and capacities of proposed equipment and placement methods. 14. Load Distribution Slab layout geometry and reinforcing steel shop drawings. E. (Type 3 Working Drawings) Manufacturer's Certificate of Compliance along with a copy of the test results showing the geofoam blocks for each material Type meet the physical properties of Table 8-33.1. Testing shall be performed by an ISO/IEC 17025:2005 accredited laboratory. Material for testing shall be obtained from production lots of the blocks used for the Project and samples for testing shall be taken per ASTM D7557. Frequency of testing shall be per Table 8.33.3. Test results shall be submitted at least 3 days prior to delivery of geofoam to the site. Table 8.33.3 EPS Geofoam Testing Frequency EPS Initial Testing Ongoing testing Type 1 block for 1 block per 600 cubic yards for EPS15 the initial 100 the next 2400 cubic yards; 1 cubic yards block per each 1200 cubic 1 block for EPS29 the initial 100 1 block per 350 cubic cubic yards yards thereafter F. The Engineer has the right to randomly sample at the manufacturing plant. If any block does not conform to the physical requirements it may be rejected by the Engineer. 8-33.3(2) Preconstruction Meeting A preconstruction meeting shall be held at least five working days before the Contractor begins Work. The meeting shall be at the site to discuss construction procedures, personnel, and equipment, and other applicable elements. Those attending shall include: • (Representing the Contractor) The superintendent, on site supervisors, all foremen, and inspection personnel. • (Representing the Contracting Agency) The Engineer, key inspection personnel, and others as determined by the Engineer. If the Contractor's key personnel change, or if the Contractor proposes a significant revision of the accepted submittal, an additional conference shall be held before construction operations are performed. 228`" UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 43 March 22, 2019 Project Number: 07-3022 8-33.3(3) General Each geofoam block shall be labeled with the Manufacturer's identification, ASTM D6817 material Type, and date of manufacture. Additional markings shall be applied as necessary by the supplier to indicate the location of placement of each block relative to the reviewed layout to ensure that the correct density (Type) of block is installed. The top two feet of geofoam blocks along Wall SW3, east of S 228t' Station 14+25.00 shall not be installed until the settlement in the adjacent structural earth wall embankment settlement period is completed. See Section 6-13.3(7) for settlement monitoring. 8-33.3(4) Protection Geofoam blocks shall be handled in a manner so as to minimize physical damage to the blocks. Prior to the delivery of geofoam to the Project site, the Contractor shall review and be thoroughly knowledgeable with the manufacturer's care and handling recommendations. Care shall be taken to prevent physical damage to geofoam blocks, including surface finishes, during delivery, storage and construction. Geofoam shall be protected from moisture and sunlight prior to installation. Geofoam fill to be exposed to daylight for more than 30 days shall be covered with opaque material to prevent ultraviolet light degradation. Discoloration and dusting of geofoam caused by extensive exposure to sunlight is a defect that will adversely affect its service is grounds for rejection. Geofoam should be considered combustible and shall not be exposed to open flame or other ignition sources. The Contractor shall protect the Geofoam blocks from: (1) Organic solvents such as acetone, benzene, and paint thinner; (2) Petroleum based solvents such as gasoline and diesel fuel. No vehicles and construction equipment shall traverse directly on the geofoam blocks. Protection of the blocks from construction vehicles and traffic from local access detours is the Contractor's responsibility. Damage to load-bearing surfaces shall be limited to less than 20% of the equivalent load bearing area of the unit. Geofoam exposed on the face of embankments prior to embankment completion and prior to permanent shotcrete facing installation shall be protected from damage and vandalism. Temporary crash barriers shall be installed to prevent vehicles operating adjacent to the embankment from impacting the geofoam. 228`" UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 44 March 22, 2019 Project Number: 07-3022 Geofoam blocks damaged during transit, handling, storage, or by the Contractor's operations shall be replaced by the Contractor at no additional cost to the Contracting Agency. 8-33.3(5) Subgrade Preparation Underlying material shall be rough graded in accordance with Section 2-03 to provide a level surface for blocks. Remove sticks, debris, and pieces protruding more than 2 inches above the graded surface. Place a leveling pad of crushed surfacing top course as shown in the Plans. At the time of placement, there shall be no standing water or accumulated snow or ice on the subgrade within the area where geofoam blocks are placed. 8-33.3(6) Geosynthetic-Reinforced Embankment Behind Geofoam Stepped embankments behind the geofoam fill shall be constructed with geosynthetic layers in accordance with the Plans and these specifications. Geosynthetic reinforcement shall also meet the strength required for stability during construction, as determined by the Contractor. 8-33.3(7) Installation Geofoam Type, as defined in ASTM D6817, relative to depth below the top surface geofoam shown in the Plans shall be as shown in Table 8- 33.4. Higher geofoam grades than indicated are allowed, but there will be no increase in payment: Table 8-33.4 Minimum Required Geofoam Type Between Walls SW2 and SW 3 All Other (Interurban Trail) Locations Depth from Top of Minimum Required Minimum Required Geofoam Block Fill Geofoam Type Geofoam Type Feet 0 - 2.0 EPS29 EPS29 > 2.0 EPS15 EPS29 The block layout shall be designed so that the following general design details are taken into account: A. Within a given layer of blocks, the vertical joints between the adjacent ends of blocks within a given row of blocks must be offset to the greatest extent practicable relative to blocks in adjacent rows. The minimum offset of blocks placed in adjacent rows of the same layer shall be 2.0 feet. 228`h UPRR Bridge & Roadway Ph 5/Smith & Madfai 8 - 45 March 22, 2019 Project Number: 07-3022 B. In order to avoid continuous joints, each subsequent layer of blocks shall be rotated on the horizontal plane 90 degrees from the direction of placement of the previous layer placed. C. The longitudinal axes of blocks for layers above and/or below a given layer must be perpendicular to the longitudinal axes of blocks within that given later f 2 degrees. Minimum thickness of any geofoam block layer is 2.0 feet. The exception is where the depth of geofoam is less than 4 feet, minimum block layer thickness shall be 1.1 feet. Adjust geofoam block dimensions to meet plan excavation, and the geometry and elevations for roadway subgrade, load distribution slab, retaining walls, and the geowall traffic barrier (moment slabs). Blocks used at the top or bottom surfaces of embankments may be trimmed to less than the minimum thickness and have edge angles deviating from 90 degrees as necessary to match the design roadway profile, cross-slopes, and horizontal alignment. Field and/or shop trimming and cutting will be required as necessitated by the geometry of the fill being constructed. The surface of a layer of geofoam blocks to receive additional geofoam blocks shall be constructed with a variation in surface tolerance of no more than 0.05 feet in any 10-foot interval. All blocks shall accurately fit relative to adjacent blocks. No gaps greater than 0.05 feet will be allowed on vertical joints. The surface of the geofoam fill beneath the load distribution slab shall be constructed to within the tolerance of zero to minus 0.2 feet. Horizontal layers of geofoam blocks shall be bonded to the next geofoam layer above (and below) with either connectors or adhesive. A. Adhesive shall be a urethane or polyurethane adhesive compatible for use with EPS geofoam and approved by the geofoam manufacturer. The adhesive shall be applied with continuous beads of adhesive spaced no greater than 18 inches apart. Adhesive shall be applied and cured in accordance with the geofoam manufacturer's recommendations. Adhesive joints shall develop a minimum of 12.3 psi shear strength in accordance with ASTM D 732 test procedures. Additional shear strength may be required for geofoam adjacent to shotcrete facing or adjacent to embankment backfill for constructability. B. Connector plates shall be galvanized steel multi-barbed plates with a lateral holding strength of at least 60 pounds when tested with EPS15 geofoam. A minimum of 2 connectors for each 4-foot x 8-foot area of geofoam shall be installed, or as recommended by the Manufacturer. Additional connectors for shear strength may be required for geofoam adjacent to shotcrete facing or adjacent embankment backfill for constructability. Connectors shall be installed by pressing firmly into the rigid foam until the connector is flush with the surface. The next geofoam block shall be placed and seated firmly before placing subsequent blocks. 2281" UPRR Bridge&Roadway Ph 5/Smith &Madfai 8 - 46 March 22, 2019 Project Number: 07-3022 Installation of the geofoam shall comply with the submitted Working Drawings. Geofoam blocks shall be cut using a hot wire. Where it is not possible to use a hot wire, a saw may be used. Blocks shall not be placed above blocks in which ice has developed on the surface. Contractor shall comply with the Manufacturer's instructions for handling, seaming and placing materials. It is the Contractor's responsibility to protect and stabilize the geofoam during construction, providing temporary ballast, bracing, guying, or other restraint, until all the blocks are built into a homogeneous mass and the roadway section and shotcrete facing are in place. Voids around pipes and conduits penetrating the geofoam may be filled with clean sand or crushed surfacing rock material suitable for filling the voids, unless otherwise shown in the Plans and Specifications. Voids or the annulus space around pipes or conduits shall not exceed 4 inches thickness (measured radially). The gaps between the geofoam and geosynthetic layers behind the geofoam shall be filled with clean sand or crushed surfacing rock material suitable for filling the gaps. Maximum particle size shall be 1/2 inch. Contractor shall coordinate details of the geofoam to receive shotcrete facing with his shotcrete subcontractor. Geofoam installation at retaining walls to receive shotcrete facing shall have sufficient horizontal strength to support the lateral and any vertical forces caused by the application of shotcrete. Layout of geofoam blocks, connections between geofoam blocks, and connectors for support of welded wire fabric in the shotcrete facing shall be determined and coordinated by the Contractor. Details shall be included in the Working Drawing submittal. It is permissible to use rebar supports (dobies) on the top surface of the geofoam to support the reinforcing steel for the load distribution slab. Geofoam blocks having damage shall be handled as follows: A. Blocks with less than one cubic foot damaged and with less than 20 percent of the total volume of the block damaged will be considered undamaged. B. Blocks with more than one cubic foot but less than 36 cubic feet of damage may be filled with sand, provided the total damage does not exceed 20 percent of the total block volume. 2281h UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 47 March 22, 2019 Project Number: 07-3022 C. Blocks with over 36 cubic feet of damage or more than 20 percent of the block volume damaged may not be used. Undamaged portions of blocks with this level of damage may be used where smaller blocks are required, provided that the entire damaged area is removed. 8-33.3(8) Geomembrane Geomembrane shall be placed at the sides, on top of, and below geofoam as shown in the Plans. Anchor geomembrane to geofoam with multi-barbed, galvanized steel geofoam block connectors. Geomembrane may be installed with a 2'-0" wide vertical laps, such that the upper geomembrane overlaps the lower geomembrane. Geomembrane shall be free from pin holes, tears, and any defects which could cause leakage of liquid through it. Damaged sheeting shall be replaced by the Contractor to the satisfaction of the Engineer at no additional cost to the Contracting Agency. Adjacent panels of geomembrane shall overlap a minimum of 2 feet. Geomembrane shall overlap such that the upgrade sheet overlaps the downgrade sheet. 8-33.3(9) Load Distribution Slab A reinforced concrete load distribution slab shall be constructed on top of the geofoam as shown in the Plans. The Contractor shall visually inspect and repair and replace all damaged areas in the geomembrane and geofoam prior to placing concrete. The slab shall extend beyond the edge of the top surface of geofoam by 4'-0" minimum unless shown otherwise in the Plans. Vertical steps in the load distribution slab shall be provided to accommodate the changes in roadway section at the driveways. The minimum thickness of the slab shall be 7 1/2 inches. The top surface of the slab shall be adjusted to slope to ensure drainage off of the slab; adjust the top surface to prevent ponding of water on the slab. Any cracks in the load distribution slab greater than 0.02 inches shall be sealed with a suitable crack sealer. Construction shall be in accordance with Section 6-02. 8-33.4 Measurement Geofoam will be measured by the cubic yard of material installed. Measurement shall be determined from the neat line volume of the in- place material. Load distribution slab and geomembrane will be measured by the square yard. 8-33.5 Payment Payment will be made in accordance with Section 1-09.1 for the following bid items: 2281" UPRR Bridge &Roadway Ph 5/Smith &Madfai 8 - 48 March 22, 2019 Project Number: 07-3022 5 JS zoo W® Washington State Department of Transportation Request for Approval q pp oval of Material [Alaskan ntract Number 7FA Number SR 9160 n/a 99 Date -- 4/16/18 ctlon/Title of Project _-- —� - ��County Way Viaduct- Replacement South Access- SR 99 ConnectionsKing ntractor - Scarsella Bros., Inc. Subcontractor - - This form shall be completed prior to submittal. If this form is not complete at time of submittal it may be returned for information that was omitted. For WSDOT Use Only For assistance in completing,see Instructions and Example Bid RAM# III Materlai or Name and Location of Fabricator, Specification PE/QPL Item Na. Product/Type Manufacturer or Pit Number Hdgtr./QPL Reference Code Code 021.01 EPS22 Ge-ioam Blocks FMI-EPS,LLC i�y ��— ��� SP262 — ----- -- Post Falls,ID 021.06 EPS Geofcam Friction Plate FMI-EPS,LLC/ ___. __ _ S P265022.04 & Post Falls,ID 2 021.01 Board Defense � �— __ ____� ____�_ _ &022.01 6Clde Technologies,Inc.I _— - SP 262 -_-- Phoenix,AZ _ 02''.Oi�( EPSt2 GeOfoam Blocks�2 FMI-EPS,LLC/ 2,SP 26 Post Falls,ID PS 2 Z, Pro ct gi e Date State Materials Engineer �� Date Acceptance A ton o es or use y Project Engineer and State Materials Laboratory 1.Acceptance Criteria: Acceptance based upon'Satisfactory'Test Report for samples of materials to be incorporated into project. 2.Acceptance Criteria: Mfg.Cert.of Compliance for'Acceptance,prior to use of material. 3.Acceptance Criteria: Catalog Cuts for'Acceptanee'prior to use of material. Catalog Cut Approved ❑yes ❑No 4,Acceptance Criteria: Submit Shop Drawings for'Approvai'prior to fabrication of material. 5.Acceptance Criteria: Only'Approved for Shipment','WSDOT Inspected'or'Fabrication Approved Decaf material shall be used. 6.Acceptance Criteria: Submit Certificate of Materials Origin to Project Engineer Office, 7.Acceptance Criteria: Request Transmitted to State Materials Laboratory for Approval Action, 8.Source Approved: 9. Approval Withheld; Submit samples for preliminary evaluation 10. Approval Withheld: 11-Miscellaneous Acceptance Criteria. Remarks. Project Engineer Distribution ❑ State Materials Engineer Distribution Contractor ❑Region Materials Q General File ❑ Engineer El Signing Inspection Region Operations En g� State Materials Lab ❑Other ❑ Fabrication Inspection M/S 47365 _ DOT Form 350-071 EF Revised i212012 I-hOI —~� EPS"u FK8I-EPS MANUFACTURES SUBMITTAL PACKAGE PROJECT SRAAAbASKAN WAY VIADUCT PRODUCT EXPANDED POLYSTYRENE GEOFOAN1 BLOCKS AND GE(lFOAM FRICTION PLATES TABLE OF CONTENTS MANUFACTURER'S CER/TF|CATEOFCOK4PLiANCE ------------ 2 GEOFOAM TECHNICAL DOCUMENTS ........ ........ .......................................... FRICTION PLATE TECHNICAL DATA.____________________._ UL EVALUATION REPORT .................................. ...... ..............._.................... BRYXREPORT ... ........ _ ...................... ....................................................... 7 OORVV REPORT...................__________________.....________ GEOFOAMSOS� --------------------'------'----'-'--1y BOARD DEFENSE TECHNICAL DATA SHEET................................................23 MANUFACTURES TEST REPORT-..... ......- GRIPPER PLATETESTDATA ....... ...... ............................ ----------- 8 CURRENT UL INSPECTION REPORT ----------- ........ .......... ........ ... ----.38 9456w McGuire Rd. Post Falls, moxua4 888-777-8485 208-777*485 pax 208-777-9527 FMI EPS. Certificate of Compliance FMI-EPS, LLC, hereby referred to as The Supplier, hereby certifies that all materials delivered adheres to standard specifications and contract documents and plans for the project listed below. The Supplier also certifies that the Geofoam blocks supplied meets or exceeds minimum requirements for physical properties per ASTM D6817. The Supplier also certifies that all geofoam materials delivered are treated with a flame retardant to meet flame and smoke developed characteristics described within the UL Listing Report UL18546-01. The material is also certified to prevent insect attacks and is protected against vector intrusion by treatment via Board Defense(Disodium Octaborate Tetrahydrate) EPA regulation number 44757-20 manufactured by Incide Technology. The Supplier also certifies that the geofoam friction plates are designed to have a lateral holding strength of 60 pounds when tested with EPS15 Geofoam. Project: SR 99 Alaskan Way Viaduct Contractor: Scarcella Bros. Specification: Roadway Excavation and Embankment Page 262 -272 Products: Geofoam, Geofoam Friction Plates Materials: Expanded Polystyrene, 22GA Galvanized Steel Plates Type(s): EPS12 Contains up to 10% regrind material EPS22 Contains up to 10% regrind material Quantity: Sufficient quantities of Geofoam blocks to fill 5,830 cubic yards of fill of EPS22. Sufficient Quantities of Geofoam Blocks to fill 550 cubic yards of fill of EPS12. Sufficient quantities of geofoam gripper plates to connect blocks together. One gripper plate for every 16 sq ft of horizontal block to block surface. Signature: Name: Anthony J. Bremer Title: Marketing and Sales Manager Company: FMI-EPS Ile Date: 1/5/2018 9456 N.McGuire Rd.Post Falls,Id.83854•888-777-8485-208-777-8485•Fax:208-777-9527 280 Rose St.Jerome,Id.83338•877-634-1307•208-324-5998•Fax:208-324-8240 FMI EPS Geofoam Blocks EPS«< Lightweight, Durable and Versatile for Geotechnical Applications �j FMI-EPS is your source for EPS (Expanded Polystyrene) Geofoam Blocks. Our staff has been working with Engineers, Designers and Contractors on EPS Geofoam projects for over 25 years. EPS Geofoam is a lightweight cellular plastic foam block used in geotechnical applications such as lightweight fill for construction on soft ground. Road embankment stability can be enhanced with a properly designed EPS Geofoam Blocks. Utilizing an interlocking stack of EPS Geofoam Blocks on a slide slope can greatly reduce horizontal movement and vertical loads. By placing EPS Geofoam Blocks directly behind retaining walls, bridge abutments or foundation walls results in a considerable reduction of lateral stress on the structure. This means less conventional materials to construct a new wall. In terms of Civil Engineering applications the use of"The EPS Geofoam Construction Method"typically translates to benefits that include Cost Effective Design, Reduced Traffic Congestion, Timely Construction Schedules and Real Dollar Savings in the overall cost of construction. The use of EPS Geofoam in engineered construction applications, is growing rapidly. EPS Geofoam Block Uses: EPS Geofoam has been successfully used in the following engineered applications: • Breams and Embankments Dikes and Levees Parking Structures • Bridge Approaches Foundations of Buildings Plaza and Residential Decks • Buried Utilities Protection Landscape Designs Railways and Runways • Compressible Inclusions Loading Docks and Ramps Retaining Walls EPS Geofoam Block Advantages Include: + Cost Effective Solution: The lightweight nature of EPS Geofoam Blocks can eliminate costly preloading, surcharging or staged construction. Given the light weight of EPS Geofoam Blocks, the need for heavy earth moving and compact equipment can be reduced or even eliminated, compared to conventional fills. On projects where poor access or rough terrains are a cost issue, EPS Geofoam Blocks can be transported, moved and placed faster than conventional fills, saving the project time and money. -I- Dependable: EPS Geofoam Blocks are manufactured in our modern manufacturing facility, with state-of-the-art equipment. This assures consistent physical properties in each individual Block that make up a typical EPS Geofoam fill system. Other lightweight fill materials such as tires, wood chips and foamed concrete can be varied and inconsistent in the make-up of their fill. This can result in a non-uniform load transfer, differential settlement, leachates and possible fire hazard. + Durable: High compressive strength makes EPS Geofoam Blocks durable and resistant to damage and shifting over time. -I- Environmentally Safe: EPS Geofoam contains no CFCs, HFC's, HCFC's, Dyes or formaldehyde. EPS is an inert and highly stable product that will not decay, decompose, or produce undesirable gases or leachates to the surrounding environment. EPS Geofoam Blocks are recyclable and safe for waste-to-energy (WTE) systems and landfills. -I- Insect and Mold Resistant: EPS Geofoam Blocks can be manufactured with an inert non-polluting additive that repels termites and carpenter ants. EPS Geofoam is inert, it does not sustain mold and or mildew growth. FMI-EPS, LLC 9465 N. McGuire Rd. Post Falls, ID 83854 USA Ph: 208-777-8485 888-777-8485 280 Rose Street Jerome, ID 83338 USA Ph: 208-324-5998 www.fmi-eos corn FMI EPS Geofoam Blocks , f EPS- Lightweight, Durable and Versatile for Geotechnical Applications + Low Density/ High Strength: The Density of EPS Geofoam ranges from 1 to 2.85 Ib/ft3, which equates to 1/100th the weight of soil and rock, making it a superior, ultra lightweight fill system that significantly reduces the stress on underlying sub grades. The lighter load reduces the settlement and increases the stability against bearing and slope failures. + Low Interface Friction: In direct shear tests the interface friction between sand and EPS Geofoam is comparable to the internal friction of sand alone. + Predictable and a Proven Performer: For over 35 years engineers, designers and contractors have been using EPS Geofoam Blocks worldwide. EPS Geofoam meets ASTM D6817, "Standard Specification for Rigid Cellular Polystyrene Geofoam." It is currently approved for use by numerous state Departments of Transportation (DOT), and the Federal Highway Administration (FHWA).We can assist you in determining what grade of EPS Geofoam Blocks will meet your project requirements. EPS Geofoam Blocks can stand up to all industry tests...and it has. + Maximize Onsite Installation Efficiency: EPS Geofoam Blocks arrive on the jobsite on your schedule, ready to be installed, NO weather delays. Other fill material such as wood chips, saw dust, foamed concrete and soil can be weather sensitive during installation, putting your project behind schedule. + No Maintenance: Under normal conditions, a project that uses EPS Geofoam Blocks requires no maintenance for the life of the project fill system. + Thermal Insulation: EPS Geofoam Blocks are 98-99% air by volume, making it a highly efficient thermal insulator. EPS Geofoam Block Product Features: + Adaptable: EPS Geofoam Blocks come precut from our plant, but they can be easily cut and or fabricated on the jobsite with a hot-wire cutter or a saw. + Custom Project Specific Sizes: EPS Geofoam Blocks, are manufactured to meet project specific requirements. We have the capability to manufacture various block sizes, depending on your project's requirements. Please don't hesitate to contact us to determine the most cost effective size for your next project. + Production Identification: Each EPS Geofoam Block is clearly labeled, showing the date the Block was manufactured, ASTM designation, density and our UL 3rd party label. I� FMI-EPS, LLC 9465 N. McGuire Rd. Post Falls, ID 83854 USA Ph: 208-777-8485 888-777-8485 280 Rose Street Jerome, ID 83338 USA Ph: 208-324-5998 www.fmi-eps.corn FMI EPS Geofoam Blocks & Construction Method is the Solution to these Common Problems EPS,, Bridge Abutments Retaining Walls Lightweight Fill Lightweight Fill Ilk Freeways & Roads Foundations Lightweight Fill Elevation Changes J Side Hills Stadium Seating Widening Embankments Widening&Raising EPS Geofoam Fill System Design Recommendations: -rr7= ♦ For EPS Geofoam applications. The design load stresses should not exceed 1% strain for the combined live and dead loads. + In applications where the EPS Geofoam fill will be subject to vehicular traffic, a Load Distribution Slab, (min.6 inches) is Weight Reduction Weight Reduction recommended under the road subbase. for Structures for Utilities Protection -+- In regions where differential icing may occur(e.g., bridges and overpasses)a well graded subbase should be provided.A well graded subbase will contain a high degree of fines and will retain moisture.A subbase thickness of 20"to 32" over the EPS Geofoam Blocks is adequate for most designs. -+- In applications where the EPS Geofoam fill is periodically subject to submergence from flooding or fluctuating ground water, uplift EPS Geofoam Fill System Makes Sense: buoyancy force must be counteracted with proper overburden or other restraint devices with geogrids or geomembranes. Extremely lightweight to reduce lateral and or bearing loads. Predictable engineered product performance,forover40years. -+-FMI-EPS recommends that the complete EPS Geofoam Fill Wide range of strength available to meet specific project requirements. System be completely designed and reviewed by a Licensed Civil Not weather sensitive,can be installed in various weather conditions. Engineer. Cost effective solution,saves money and time. FMI-EPS, LLC 9465 N. McGuire Rd. Post Falls, ID 83854 USA Ph: 208-777-8485 888-777-8485 280 Rose Street Jerome, ID 83338 USA Ph: 208-324-5998 www.fmi-el)s.com Table 1 Physical Properties of FMI-EPS Geofoam Blocks* TYPE-ASTM D 6817 EPS12 EPS15 EPS19 EPS22 EPS29 EPS39 EPS46 Density,min. Ib/ft' 0.70 0.90 1.15 1.35 1.80 2.40 2.85 (kg/m') (11.2) (14.4) (18.4) (21.6) (28.8 (38.4) (45.7) Compressive Resistance* Psi 2 3.6 5.8 050_73 10.9 15.0 18.6 @ 1%deformation,min. Psf 320 520 840 1050 1570 2160 2680 (kPa) (15) (25) 1 (40) (50) - (75) (103) (128) Elastic Modulus psi 220 360 580 730/ 1090 1500 1860 (kPa) (1500)* (2500) {4000) (5000) (7500) (10300) (12800) Flexural Strength min. psi 10.0' 25.0 30.0 40.0 50.0 60.0 75.0 (kPa) (69) (172) (207) (276) (345) (414) (517) Water Absorption volume P <4.0 < 4.0 <3.0 < 3.0 < 2.0 <2.0 < 2.0 Oxygen Index,min. volume 24.0 24.0 24.0 24.0 l 24.0 24.0 24.0 % Buoyancy Force Ib/ft' 61.7 61.5 61.3 61.1 60.6 60.0 59.5 (kg/m') (990) (980) (980) (980) (970) (960) (950) Poisson's Ratio - .05 .05 .05 .05 .05 05 05 Coefficient of Friction - .6 .6 .6 .6 6 Dimensional Stability (max.'/o) <2% <2% <2% < 2% < 2% < 2% < 2°' ,o Additional Properties for Compressible Applications Compressive Resistance- psi 5.1 8.0 13.1 16.7 24.7 35.0 43.5 min.@ 5%deformation (kPa) (35) (55) (90) (115) (170) (241) (300) Compressive Resistance; psi 5.8 10.2 16 19.6 29 40.0 50.0 min.@ 10%deformation (kPa) (40) (70) (110) (135) (200) (276) 1 (345) 'See ASTM D6817 Standard for test methods and complete information. "Properties are based on data provided by Resin Manufactures,Independent Test Agencies and FMI-EPS. 16 S . 73� Imperial 1 Metric Conversion Length 1 foot 0.308 meter Force 1 pound force 4.448 Newton '- .�, .. Stress 1 pound force per square foot (psf) 47.88 Pascal 1 pound force per square inch (psi) 6.898 kilopascal (kPa) FMI a _ U F M The informations this believed tbulletin is presented in EPS 1Y O good faith.and is believed to be accurate.All " �J statements are made without warranty 1 hwkienAszocrotiw, �L°`° APPROVED expressedorimphed. 9465 N. McGuire Rd. Post Falls, ID 83854 USA Ph: 208-777-8485 888-777-8485 EPS, 280 Rose Street Jerome, ID 83338 USA Ph: 208-324-5998 wwvv.fIj1i-�s._conl The EPS Geofoam Friction Plate t The Friction Plate increases the interface friction, while maintaining and stabilizing EPS Geofoam Blocks in a one step application. The EPS Geofoam Friction Plate is a 22 gauge galvanized steel, two-sided-barbed plate made in the USA. It is used to "lock in"or restrain the EPS Geofoam Blocks from moving horizontally between the layers of EPS Geofoam Fill. Its unique design keeps the block from shifting during inclement weather conditions, as well. The design of the Friction Plate (4"x 4")exhibits a lateral holding strength of approximately 60 lbs. All projects are unique in design and method.Therefore it is the responsibility of the designer/applicator to calculate the load requirements of the project for determining the proper number of Friction Plates needed. However a minimum of 1 plate for every 16 sq.ft. of EPS Geofoam Block surface is recommended. Installation: -F Place the EPS Geofoam Friction Plate as shown on plans and specifications. -f- Press firmly into the Geofoam Block until the plate is flush with the surface. (Use a 1"wooden dowel for cost-effective setting tool) f Position the top Geofoam Block as specified. • Walk on top of the block, setting it firmly downward before other work continues. • Repeat this procedure for each layer. • Remember to offset or stagger all vertical and horizontal joints of the EPS Geofoam Block Fill. FMI C_Q' 'I 1 The information in this bupetin is presented in good faith,and is believetl to be accurate.All statements are made without warranty NaMcrs Associofion 01SQ APPROVED expressed or implied. 9465 N. McGuire Rd. Post Falls, ID 83854 USA Ph: 208-777-8485 888-777-8485 EPS I« 280 Rose Street Jerome, ID 83338 USA Ph: 208-324-5998 www.fmi-eps com UL Evaluation Report UL ER18546-01 Issued: October 31, 2013 Revised: November 18, 2015 Visit UL's On-Line Certifications Directory:www.ul.com/erdirectory for current status of Report. UL Category Code: ULEX CSI MasterFormat® DIVISION: 07 00 00 -THERMAL AND MOISTURE PROTECTION Sub-level 2: 07 20 00 -Thermal Protection Sub-level 3: 07 21 00 -Thermal Insulation Sub-level 4: 07 21 13 - Board Insulation Sub-level 3: 07 22 00 - Roof and Deck Insulation Sub-level 4: 07 22 16 - Roof Board Insulation DIVISION: 31 00 00 - Earthworks Sub-level 3: 31 23 00 - Excavation and Fill Sub-level 4: 31 23 23 - Fill COMPANY: FMI-EPS, LLC 9456 NORTH MCGUIRE RD POST FALLS, ID 83854 www.fmi-eps.com 1. SUBJECT: FMI EPS INSULATION BOARDS FMI EPS GEOFOAM BLOCKS Underwriters Laboratories Inc 333 Pfingsten Road,Northbrook,IL 60062-2096 USA T 847,272 8800/F:84T272-8129/W:ULcom 2. SCOPE OF EVALUATION: ■2012 International Building Code®(IBC) ■2012 International Residential Code®(I RC) ■2012 International Energy Code®(IECC) ■ICC-ES Acceptance Criteria for Foam Plastic Insulation (AC12), dated June 2012 ■ICC-ES Acceptance Criteria for Termite Resistant Foam Plastic(AC239), dated November 2008 ■ICC-ES Acceptance Criteria for Quality Documentation (AC10), dated June 2014 The products were evaluated for the following properties: FMI EPS Insulation Boards: ■Surface Burning Characteristics (ANSI/UL723, ASTM E84) ■Physical Properties(ASTM C578) ■Roofing Systems for Exterior Fire Exposure(ANSI/UL790, ASTM El08) ■Flammability Testing for Use in Attics and Crawl Spaces (AC12, App. A and B) ■Termite Resistance(AC239) FMI EPS Geofoam Blocks: ■Surface Burning Characteristics (ANSI/UL723, ASTM E84) ■Physical Properties (ASTM D6817) ■Foam Plastic-Special Approval (ANSI/UL1715) ■Termite Resistance (AC239) 3. REFERENCED DOCUMENTS ■ICC-ES Acceptance Criteria for Foam Plastic Insulation (AC12), dated June 2012 ■ICC-ES Acceptance Criteria for Termite Resistant Foam Plastic(AC239), dated November 2008 ■ICC-ES Acceptance Criteria for Quality Documentation (AC10), dated December 2012 ■ANSI/UL723(ASTM E84), Test for Surface Burning Characteristics of Building Materials ■ANSI/UL790(ASTM El08), Standard Test Methods for Fire Tests of Roof Coverings ■ANSI/UL1715, Fire Test of Interior Finish Material ■ASTM C578, Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation ■ASTM D6817, Standard Specification for Rigid Cellular Polystyrene Geofoam ■ASTM D7180, Standard Guide for Use of Expanded Polystyrene(EPS)Geofoam in Geotechnical Projects ■ASTM D7557, Standard Practice for Sampling of Expanded Polystyrene Geofoam Specimens 4. USES 4.1 FMI EPS Insulation Boards (ASTM C578 Types I, Vlll, II, IX,XIV, and XV): FMI EPS Insulation Boards are used as nonstructural insulation on the interior or exterior of above grade walls, on the interior or exterior of below grade walls, below concrete slabs, around concrete slab edges, or as roof insulation. Installation shall be in accordance with Section 6.2 of this report. Page 2 of 9 The insulation boards may be used on walls in attics and crawl spaces when installation is in accordance with Section 6.2.3. 4.2 FMI EPS Geofoam Blocks (ASTM D6817 Types EPS15, EPS19, EPS22, EPS29, EPS39, and EPS46): FMI EPS Geofoam Blocks are used as lightweight structural fill in floor cavities. Installation shall be in accordance with Section 6.3 of this report. S. PRODUCT DESCRIPTION 5.1 General: FMI EPS Insulation Boards, and FMI EPS Geofoam Blocks described in 5.2, and 5.3 are molded, closed- cell expanded polystyrene having a flame spread index not exceeding 25 and a smoke developed index not exceeding 450 for thicknesses up to 6 inches when tested in accordance with UL723 (ASTM E84) as required by Section 2603.3 of the IBC or Section 316.3 of the IRC, as applicable. All products described in this report have been treated for termite resistance in accordance with Section 2603.9 exception 2 of the IBC or Section R318.4 exception 2 of the IRC. 5.2 FMI EPS Insulation Boards (Types I, Vlll, II, IX, XIV, and XV): FMI EPS Insulation Boards have been found to comply with ASTM C578. The boards are manufactured at minimum densities of 0.90, 1.15, 1.35, 1.80, 2.40, and 3.00 Ibs/ft3 and have ASTM C578 designations of Type I, Type Vlll, Type ll, Type IX, Type XIV, and Type XV respectively. See excerpt from ASTM C578, Table 1 below: Table 1 —Thermal Resistance Values ASTM TYPE DENSITY, min., Ib/ft3 THERMAL RESISTANCE ', min., Type I ° F-ft2-h/Btu 0.90 3.6 Type VIII 1.15 3.8 Type 11 1.35 4.0 Type IX 1.80 4.2 Type XIV 2.40 4.2 =txv 3.00 4.3 'Thermal resistance(R)values are based on tested values at 1 inch thickness and 75F mean temperature and must be multiplied by the installed thickness for thicknesses greater than 1 inch. Page 3 of 9 5.3 FMI EPS Geofoam Blocks (Types EPS15, EPS19, EPS22, EPS29, EPS39, and EPS46): FMI EPS Geofoam Blocks have been found to comply with ASTM D6817. The blocks are manufactured at minimum densities of 0.90, 1.15, 1.35, 1.80, 2.40, and 2.85 Ibs/ft3and have ASTM D6817 designations of EPS15, EPS19, EPS22, EPS29, EPS39, and EPS46 respectively. See excerpt from ASTM D6817, Table 2 below: Table 2—ASTM D6817 Physical Property Requirements for RCPS Geofoam ASTM TYPE DENSITY, min., Ib/ft3 COMPRESSIVE RESISTANCE, min., psi Type EPS15 0.90 at 1 % 3.6 Type EPS19 1.15 5.8 Type EPS22 1.35 7.3 Type EPS29 1.80 10.9 Type EPS39 2.40 15.0 Type EPS46:j::::::— 2 85 18.6 6. INSTALLATION 6.1 General: FMI EPS Insulation Boards, and FMI EPS Geofoam blocks are installed in accordance with the manufacturer's published installation instructions and this evaluation report. The manufacturer's published installation instructions and this report must be strictly adhered to, and a copy of the instructions shall be available on the jobsite during installation. 6.2 FMI EPS Insulation Boards: FMI EPS Insulation Boards must be attached to the structure in a manner that will hold the insulation securely in place. The insulation boards must not be used structurally to resist transverse, axial or shear loads. The interior of the building must be separated from the FMI EPS Insulation Boards with a thermal barrier as required by Section 2603.4 of the IBC or Section R316.4 of the IRC, as applicable. FMI EPS Insulation Boards may be used as vapor retarders based on perm values described in Tables 3, when required in accordance with the applicable sections of the IBC, IRC and IECC. Vapor retarders are classified as follows: Class I: 0.1 perm or less Class II: 0.1 <perm s 1.0 Class III: 1.0<perm 5 10 perm Page 4 of 9 Table 3—Water Vapor Permeance of FMI EPS Insulation Boards ASTM TYPE DENSITY, min., Ib/ft3 MAXIMUM PERM ', Type 1 0.90 5.0 Type VIII 1.15 3.5 Type II 1.35 3.5 Type IX 1.80 2.5 Type XIV 2A0 2.5 Type XV 3.00 2.5 ' Water vapor permeance values are based on 1 inch thickness when tested in accordance with ASTM C578 and ASTM E96. Actual water vapor permeance values may be calculated based on insulation thickness, by dividing the perm value shown by the installed thickness in inches. 6.2.1 FMI EPS Insulation Boards used on the exterior of above grade walls: FMI EPS Insulation Boards are used on the exterior of above grade walls as follows: • Exterior Walls of One-and Two-Family Dwellings in accordance with the 2012 IRC, • Exterior walls of one story buildings of Types I, II, III, or IV construction in accordance with Section 2603.4.1.4 of the IBC, • Exterior walls of Type V construction in accordance with Section 2603.2, 2603.3, and 2603.4 of the IBC 6.2.2 FMI EPS Insulation Boards Used in Roofing: FMI EPS Insulation Boards are used as a roofing insulation as part of a UL Classified Class A, B or C roof-covering assembly in accordance with UL 790. 6.2.3 FMI EPS Insulation Boards Used in Attics and Crawl Spaces: FMI EPS Insulation Boards may be used on walls of attics and crawl spaces, without the coverings listed in Section 2603.4.1.6 of the IBC or Sections R316.5.3 and R316.5.4 of the IRC, as follows: 1. Entry to the attic or crawl space is limited to service of utilities, and no storage is permitted. Utilities include, but are not limited to, mechanical equipment, electrical wiring, fans, plumbing, gas or electric hot water heaters, and gas or electric furnaces. 2. There are no interconnected crawl space areas 3. Air in the attic or crawl space is not circulated to other parts of the building. Page 5 of 9 4. Under-floor (crawl space) ventilation is provided when required by Section 1203.3 of the IBC or Section R408.1 IRC, as applicable. 5. Combustion air is provided in accordance with IMC Sections 701 and 703 (2006 IMC) or Section 701 (2012 and 2009 IMC). 6. FMI EPS Insulation boards are limited to a maximum thickness of 4 inches (102 mm) for Type 1, or a maximum thickness of 3-1/4 inches (82.6 mm)for Type Vill, or a maximum thickness of 2-2/3 inches(67.8 mm)for Type II, or a maximum thickness of 2 inches(51 mm)for Type IX. 6.3 FMI EPS Geofoam Blocks: FMI EPS Geofoam blocks are placed loosely on a level surface or existing structural slab. The blocks may be installed in a single layer or in multiple layers. Structural loads on the FMI EPS Geofoam blocks shall not exceed the compressive resistance at 1% in accordance with ASTM D6817. Additional design considerations are included in ASTM D7180, "Standard Guide for Use of Expanded Polystyrene (EPS) Geofoam" and ASTM D7557, "Standard Practice for Sampling of Expanded Polystyrene Geofoam Specimens". When FMI EPS Geofoam blocks are less than 4 in. in thickness, the interior of the building must be separated from the Geofoam blocks with a thermal barrier as required by Section 2603.4 of the IBC or Section R316.4 of the IRC, as applicable. When FMI EPS Geofoam blocks are greater than 4 in. in thickness, a minimum 1 in. concrete or masonry must cover the Geofoam blocks on all faces. 7. CONDITIONS OF USE 7.1 General: The FMI EPS Insulation Boards and the FMI EPS Geofoam blocks described in this report comply with, or are suitable alternatives to what is specified in those codes listed in Section 2 of this report, subject to the following conditions. The FMI EPS Insulation Boards and FMI EPS Geofoam Blocks must be produced, identified, and installed in accordance with the manufacturer's published installation instructions. If there is a conflict between this report and the manufacturer's instructions this report governs. The use of FMI Insulation Boards and the FMI EPS Geofoam blocks are not restricted in areas where the probability of termite infestation is defined as"very heavy" in accordance with Section 2603.9 of the IBC or Section R318.4 of the IRC, as applicable. 7.2 FMI EPS Insulation Boards: The FMI EPS Insulation Boards must be separated from the building interior with a thermal barrier, such as 112 in. gypsum board, as required by Section 2603.4 of the IBC or Section R316.4 of the IRC, as applicable. For FMI EPS Insulation Boards: See UL Online Certifications Directory for Class A, B or C roof-covering assemblies UL Classified in accordance with UL 790(TGFU). See UL Online Certifications Directory for foamed plastic UL Classified in accordance with UL 723 (BRYX). Page 6 of 9 See UL Online Certifications Directory for rigid cellular polystyrene thermal insulation UL Classified in accordance with ASTM C578(QORW). 7.3 FMI EPS Geofoam Blocks: FMI EPS Geofoam Blocks less than 4 in. in thickness must be separated from the building interior with a thermal barrier such as '/ in. gypsum board, as required by Section 2603.4 of the IBC or Section R316.4 of the IRC, as applicable. FMI EPS Geofoam Blocks greater than 4 in. in thickness must be separated from the building interior with a minimum 1 in. thick concrete or masonry on all faces as required by Section 2603.4.1.1 of the IBC. Design loads to be resisted by the FMI EPS Geofoam Blocks must be determined in accordance with the IBC or IRC, as applicable, and must not exceed the allowable loads noted in this report. All construction documents specifying the FMI EPS Geofoam Blocks must comply with the design limitations of this report. Design calculations and details for the specific applications must be furnished to the code official, verifying compliance with this report and applicable codes. The documents must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 7.4 Manufacturing Locations: The products are manufactured at the following locations described in Table 4under the UL LLC Listing or Classification and Follow-Up Service Program, which includes audits in accordance with ICC-ES Acceptance Criteria for Quality Documentation, AC 10. Table 4—Manufacturing Locations LISTEE LOCATION PLANT ID NO. FMI-EPS,LLC 9456 N MCGUIRE RD POST FALLS, ID 83854 none 8. SUPPORTING EVIDENCE 8.1 FMI EPS Insulation Boards: 8.1.1 Data in accordance with ICC-ES Acceptance Criteria for Foam Plastic Insulation (AC12), dated June 2012. 8.1.2 UL Classification reports in accordance with UL 723, ASTM C578, and UL 790, . See UL Product Certification Categories(BRYX), (QORW), and(TGFU), respectively See UL's On-Line Certification Directory for the following Product Categories: • BRYX • QORW • TGFU 8.1.3 Data in accordance with ICC-ES Acceptance Criteria for Termite Resistant Foam Plastics (AC239), dated November 2008, 8.1.4 Documentation of quality system elements described in AC10. Page 7 of 9 8.2 FMI EPS Geofoam Blocks: 8.2.1 UL Classification in accordance ith UL 723, ASTM D6817, and UL1715. See UL Product Certification Categories(BRY (QORW)and(OERU), respectively. See UL's On-Line Certification Directory for BRYX and QORW, above in section 8.1.2 and as follows for: • OERU 8.2.2 Data in accordance with ICC-ES Acceptance Criteria for Termite Resistant Foam Plastics (AC239), dated November 2008. 8.2.3 Documentation of quality system elements described in AC10. 9. IDENTIFICATION The FMI EPS Insulation Boards and FMI EPS Geofoam Blocks described in this evaluation report are identified by a marking bearing the report holder's name(FMI-EPS), the plant identification, the product name, the ASTM type designation, the UL Classification Mark, and the evaluation report number UL ER18546-01. The validity of the evaluation report is contingent upon this identification appearing on the product or UL Classification Mark certificate. 10. USE OF UL EVALUATION REPORT 10.1 The approval of building products, materials or systems is under the responsibility of the applicable authorities having jurisdiction. 10.2 UL Evaluation Reports shall not be used in any manner that implies an endorsement of the product, material or system by UL. 10.3 The current status of this report, as well as a complete directory of UL Evaluation Reports may be found at UL.com via our On-Line Certifications Directory: www.ul.com/erdirectory Page 8 of 9 ©2015ULLLC This UL Evaluation Report is not an endorsement or recommendation for use of the subject and/or Product described herein. This report is not the UL Listing or UL Classification Report that covers the subject product. The subject product's UL Listing or UL Classification is covered under a separate UL Report. UL disclaims all representations and warranties whether express or implied, with respect to this report and the subject or product described herein. Contents of this report may be based on data that has been generated by laboratories other than UL that are accredited as complying with ISO/!EC Standard 17025 by the International Accreditation Service (1AS) or by any other accreditation body that is a signatory to the International Laboratory Accreditation Cooperation (ILAC) Mutual Recognition Arrangement(MRA). The scope of the laboratory's accreditation shall include the specific type of testing covered in the test report. As the accuracy of any non-UL data is the responsibility of the accredited laboratory, UL does not accept responsibility for the accuracy of this data. U L Page 9 of 9 I��INLINE CERTIFI ATtON OIREGTORY �•o/ BRYX.R 18546 Foamed Plastic Paae Bottom Foamed Plastic See General Information for Foamed Plastic FMI-EPS L L C 9456 N MCGUIRE RD R18546 POST FALLS,ID 83854-6119 USA Foamed plastic in the form of boards. 6 In.Max+ Flame spread 20# Smoke developed 300# +Installed in a thickness or stored in an effective thickness,as indicated,for a density of 1.00-2.00 lb/cubic ft. #Flame spread and smoke developed recorded while material remained in the original test position.Ignition of molten residue on the furnace floor resulted in flame travel equivalent to calculated flame spread classification of 140 and smoke developed classification of over 500. a t odatgd on 2013-05-06 Ouesti n ? Print this o Terms of = Paae Too ©2015 UL LLC When the UL Leaf Mark is on the product,or when the word"Environment"is included in the UL Mark,please search the UL Environment database for additional information regarding this product's certification. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service.Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service.Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1.The Guide Information,Assemblies,Constructions,Designs,Systems,and/or Certifications(files)must be presented in their entirety and in a non-misleading manner,without any manipulation of the data(or drawings).2.The statement"Reprinted from the Online Certifications Directory with permission from UL"must appear adjacent to the extracted material.In addition,the reprinted material must include a copyright notice in the following format: "©2015 UL LLC". u� ONLINE CERTIFICATIONS OIREGTORT Q0RW.R18546 Polystyrene Thermal Insulation, Rigid Cellular Page Bottom Polystyrene Thermal Insulation, Rigid Cellular See General Information for Polystyrene Thermal Insulation Rigid Cellular FMI-EPS L L C 9456 N MCGUIRE RD R18546 POST FALLS,ID 83854-6119 USA Cellular polystyrene in the form of blocks or boards,Types I,II,VIII,IX,XIV and XV,in accordance wih ASTM C578 Cellular polystyrene(geofoam)in the form of blocks or boards,Types EPSI5,EPS19,EPS22,EPS29,EPS39 and EPS46,in accordance with ASTM D6817. Lacr UpJared on 2013-05-06 Questions? Print this oa Terms of se Page Too ©2015 UL LLC When the UL Leaf Mark is on the product, or when the word"Environment"is included in the UL Mark,please search the UL Environment databas for additional information regarding this product's certification. The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service.Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service.Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1.The Guide Information,Assemblies,Constructions,Designs,Systems,and/or Certifications(files)must be presented in their entirety and in a non-misleading manner,without any manipulation of the data(or drawings).2.The statement"Reprinted from the Online Certifications Directory with permission from UL"must appear adjacent to the extracted material.In addition,the reprinted material must include a copyright notice in the following format: "©2015 UL LLC". MATERIAL SAFETY DATA SHEET FOAM MOLDERS, INC. HAZARD RATING: 0=MINIMAL 1 =SLIGHT HEALTH 0 2 =MODERAGE FIRE 2 3 =SERIOUS REACTIVITY 0 4=SEVERE i I. PRODUCT INFORMATION PRODUCT: EXPANDED POLYSTYRENE PRODUCT GRADES: TYPE I, VIII, II & IX(BASED ON PCF DENSITY) CHEMICAL FAMILY: POLYSTRENE THERMOPLASTICS CAS REGISTRY: 9003536 FORMULA: C6 H5 TSCA INVENTORY STATUS: LISTED I II. INGREDIENTS: HAZARDOUS COMPONENTS: CAS REGISTRY NO: APPROX. % WEIGHT PENTANE 109660 1 HALOGEN FLAME RETARTANTS N/A 1% NON-HAZARDOUS COMPONENTS: POLYSTYRENE 9003536 98% III. PHYSICAL DATA FORM: RIGID CELLULAR FOAM BLOCKS BOARDS AND SHAPES COLOR: WHITE ODOR: VERY SLIGHT HYDROCARBON SCENT BOILING POINT: N/A MELTING POINT: SOFTENS AT 175 DEGREES TO 220 DEGREES F. SPECIFIC GARVITY: DENSITY .75-2.0 PCF. VAPOR PRESSURE: N/A VOLATILES BY VOLUME: LESS THAN 1%IN PENTANE AND WATER VAPOR DENSITY: N/A EVAPORATION RATE: N/A SOLUBILITY IN WATER: INSOLUBLE III. FIRE AND EXPLOSION DATA FLASH POINT AND METHOD USED: 610 F. MINIMUM (ASTM D 1929) f SPECIAL FIRE FIGHTING INSTRUCTIONS: USE APPROVED SELF- CONTAINED BREATHING APPARATUS RESPIRATOR AND PERSONAL PROTECTIVE CLOTHING. EXTINGUISHING MEDIA: WATER, CARBON DIOXIDE, AND DRY CHEMICALS. AUTOIGNITION TEMPERATURE HAZARDS: 850 DEGREES F. USUAL FIRE AND EXPLOSION HAZARDS: MAY PRODUCE A DENSE BLACK SMOKE. THE SMOKE CONSISTS OF CARBON, CARBON MONOXIDE, CARBON DIOXIDE AND WATER. THE DUST GENERATED BY FABRICATION CAN INCREASE THE FIRE HAZARD AND SHOULD BE HANDLED ACCORDINGLY. V.REACTIVITY DATA SOLUBILITY CONDITIONS: MATERIAL IS STABLE. SHOULD AVOID FIRE AND HIGH TEMPERATURES. INCOMPATABILITY: MATERIAL WILL DISSOLVE IN MOST ORGANIC SOLVENTS AND SOME INSECTICIDES,ALDEHYDES AND AMINES. HAZARDOUOS DECOMPOSITION: CARBON MONOXIDE, CARBON DIOXIDE,AND CARBON WATER HYDROGEN HALIDE. HAZARDOUS POLYMERIZATION: NONE. VI.HEALTH HAZARDS AND FIRST AID PRINCIPAL HEALTH HAZARDS AND SIGNS & SYMPTOMS OF EXPOSURE EYE CONTACT: DUST OR PARTICLES MAY CAUSE EYE IRRITATION AND/OR INJURY. FIRST AID: RINSE WITH CLEAN WATER. REMOVE FOREIGN PARTICLES WITH CLEAN LINT-FREE CLOTH. OBTAIN MEDICAL ATTENTION IF PAIN, BLINKING, TEARS OR REDNESS PERSIST. INHALATION: DUST FROM MECHANICAL FABRICATION OR SMOKE FROM HOT-WIRE CUTTING MAY CAUSE UPPER RESPIRATORY IRRITATION. FIRST AID: MOVE TO FRESH AIR IF OVERCOME BY EXPOSURE. IF NECESSARY, PROVIDE OXYGEN AND ARTIFICIAL RESPIRATION AND GET MEDICAL ATTENTION. SKIN CONTACT: NO EXPECTED HAZARD. INGESTION: BIOLOGICALLY INERT. LARGER PARTICLES MAY ACT AS AN OBSTRUCTION IF SWALLOWED. CARCINOGENICY: NONE SAFETY PRECAUTIONS: USE POSITIVE VENTILLATION. MECHANICAL FABRICATION REQUIRES THE USE OF SAFETY GLASSES OR GOGGLES AND A DUST MASK. VII. EMPLOYEE PROTECTION PERSONAL PROTECTIVE EQUIPMENT: RESPIRATORY PROTECTION: USE DUST MASK WHEN SAWING OR SANDING. SKIN PROTECTION: NONE REQUIRED. EYE PROTECTION: USE APPROVED SAFETY GLASSES OR GOGGLES WHEN SANDING OR SAWING. GENERAL CONTROL MEASURES: USE POSITIVE VENTILATION AND SAFETY GOGGLES AND DUST MASK WHEN SANDING OR SAWING. VIII. SPILL OR LEAK PROCEDURES SPILL, LEAK, OR RELEASE PROCEDURES: NORMAL GOOD HOUSEKEEPING SHOULD BE OBSERVED. MATERIAL SHOULD BE SWEPT UP AND DISPOSED OF PROPERLY. REPORTABLE QUANTITY: NONE DISPOSAL METHOD: RECYCLE, INCENERATE OR SEND TO A LANDFILL PER LOCAL AND STATE REGULATIONS. IX. SPECIAL PRECAUTIONS STORAGE AND HANDLING: ALTHOUGH THIS CONTAINS A FIRE RETARDENT ADDITIVE, EXPANDED POLYSTYRENE IS CONSIDERED TO BE CONBUSTIBLE AND ADEQUATE PROTECTION SHOULD BE TAKEN TO KEEP IT FROM A SOURCE OF IGNITION. TRANSPORTATION REQUIREMENTS: MATERIAL IS NOT A D.O.T. "HAZARDOUS MATERIAL". CONTACT: FOAM MOLDERS, INC. 9456 N MCGUIRE RD. POST FALLS, ID 83854 1-888-777-8485 FAX: 208-777-9527 THIS INFORMATION IS PROVIDED AS A GENERAL REFERENCE. TO THE BEST OF OUR KNOWLEDGE THIS INFORMATION IS COMPLETE AND ACCURATE. k Technical Data Sheet BOARD DEFENSE® (Insecticide, Termiticide and Fungicide) TECMNOLOOIEf,INC. SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Brand Name BOARD DEFENSE® Manufacturer InCide Technologies, Inc. Chemical Formula Na2B80134H2O 50 N. 41"Avenue Chemical Name/Synonyms Disodium Octaborate Tetrahydrate Phoenix, AZ 85009 Chemical Family Inorganic Borates EMERGENCY PHONE NUMBERS CAS Registry No. 12280-03-4 CHEMTREC 9300 TSCA Inventory No. 12008-41-2(anhydrous form 602-233-0756 EPA Pesticide Reg. No. 44757-20 � INCIDE TECHNOLOGIES 602-233-0756 Effective date January 1, 2016 SECTION 2 — TYPICAL PROPERTIES The following properties are typical of normal production. CHEMICAL ANALYSIS SCREEN ANALYSIS Typical Analysis US Std, Typical Percent Sodium Oxide (Na20) 14.2% Sieve No, Cumulative Boron Oxide a +200 g (6203) 67.3 /o Water of Crystallization (1-120) 17.6% Sulfate (SO4) 600 ppm BULK DENSITY Chloride (CI) 500 ppm 31 Ib/ft3 Poured Iron (Fe) 6 ppm SECTION 3 — THEORETICAL PROPERTIES The following properties are textbook theoretical data and are provided for convenience and reference only. These properties are not normally tested for the commercial product and no representation is made relative to the commercial product. THEORETICAL COMPOSITION SOLUBILITY IN WATER AS Na2B8013-4H2O Temperature Percent by Weight Of Percent °C OF Saturated Solution Boric Oxide (B203) 67.5% 0 32 Sodium Oxide (Na20) 15.0% 10 5.2 Water ofC Crystallization o 50 14.2 rY (H20) 17.5 /0 20 68 14.8 pH Of Aqueous Solutions 30 86 22.8 40 104 26.7 Percent Na2B80,34H2O pH at 50 122 By Weioht Of Solution 23°C(73.4°FJ 42.4 6 1 0 140 .1 8.5 2 8.4 5 8.0 10 7.6 15 7.3 SECTION 4 - APPLICATIONS Insecticide,termiticide,and fungicide for control of wood destroying insects and rot. Mold control agent in cellulose insulation. Flame retardant and mold control agent in the paint industry. Flame and mold retardant for timber impregnation,and in ceramics and glass industry where a high B203 to Na20 ratio is desired. SECTION 5 — PACKAGING AND HANDLING 45 pound(20.43 kg)multiwall plastic lined paper bags palletized and stretch wrapped. Fifty(50)bags per pallet. Also available in 25 lb. pails (48 pails/pallet) and one pound bottles (12 bottles/case, 42 cases/pallet). Information concerning the handling and use of this product is provided in a material safety data sheet (MSDS). This MSDS must be fully read and understood prior to any exposure, handling,or use of the product. Information presented herein has been compiled from sources considered dependable and is accurate and reliable to the best of our knowledge and belief, but it is not guaranteed to be so. Nothing herein is to be construed as recommending any practice or any product in violation of any law or regulation. It is the user's responsibility to determine the suitability of any material for a specific purpose and adopt necessary safety precautions. We make no warranty as to results to be obtained in using any material and,since conditions or use are not under our control, we must necessarily disclaim all liability with respect to use of any material supplied by us. Replaces:January 1,2009 FMI- EPS QC Compression Testing Geofoam EPS 22 Job#:I Block 24D Date Expanded: 5/9/2017 Date Molded 15/10/2017 EPS Minimum Density: 1.35 Date/Time Sampled: 1/11/2018 11:31 Tanya Garrett Sample# Weight Depth Width Height Reading at Reading at Volume Density 1% 5% 1 (g) (in) (in) (in) 1% — 5% (in ) (I b/f') 7.3 16.7 I'PSI/cf/lb Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 Al 2.822 1.595 1,996 1.983 33.56 79.12 6,3131 1.70 10-54 24,85 14.63 A2 2,876 1.999 2.019 1.997 30.74 77.14 8,0599 136 7,62 19.11 14.10 2.857 2,022 1,996 1,960 1 30.88 75,32 7,9104 1.37 7.65 1&66 13,60 A4 2.887 1,955 2.020 1.956 32.88 75.56 7 7244 142 8.33 19.13 1347 AS 2.911 1.965 2,019 1.967 27.22 77.56 19.55 13,79 Avg 2.871 1.907 2,010 1.973 1.45 8.20 20.26 13. 1 Job## Tester: Tanya Garrett Date Sampled: January 11,2018 BI B2 B3 B4 B5 AvgStd Dey 0'. Density Job# Tester: Tanya Garrett Date sampled: January 11, 2018 C1 C2 3 C4 C5 Avg Std Dev x' Density Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 D1 D2 D4 DS Avg V t e of Density Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 El E2 E3 E4 Avg E5 A "I,, FMI-EPS 9456 N. McGuire Rd. Post Falls, ID 83854 (P) (208) 777-8485 I [FI (208) 777-9527 Page 1 FMI-EPS QC Flexural Strength Testing Geofoam EPS 22 Job#j Block#: 24D Date Expanded: 5/9/2017 Date Molded 5/10/2017 EPS Minimum Density: 1.35 Date/Time Sampled: 1/11/2018 11:31 Tanya Garrett Weight Length Width Depth Flex Volume Density Flexural Support Sample# I Deflection(g) (in) I (in) (in) Reading (in') (lb/f3) Strength 35 Span(L) Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 Al 13.640 12.000 3.154 1.003 11,42 1,6617 37.9615 1.37 53.9876 10 A2 13.724 12-000 3 148 1.003 10.23 1.6617 37.8893 1.38 48.4541 10 A3 13.690 12-000 3.137 1,001 10,47 1.6650 37-6816 1.38 49.9638 10 A4 10 10 Avg 13,685 12.000 3,146 1.002 StdDevof,Density t. 7 % 137 50.80 Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 131 10 B2 10 B3 10 B4 10 85 10 Avg "ta Dev 0` DC-Isity Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 C1 10 C2 10 C3 10 C4 10 C5 10 of Density Job 4# Tester: Tanya Garrett Date Sampled: January 11, 2018 D1 10 D2 10 D3 10 D4 10 DS 10 Stcl Dev of Density Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 El 10 E2 10 E3 10 E4 10 E5 IC St t ypensity ' PM,-EPS 9456 N. McGuire Rd. Post Falls, ID 83854 1 [P] (208) 777,8485 [F] (208) 777-9527 Page 2 �11 Qua NIN.Control Department Tester Nana:Tan}~a Garrett TEST REPORT Edited by: FAt l-FPS 1.L( Machine: SUNTORM 25,ta( Test setup rtante: t,my,ruum Tem EPS?? ""I'm T,awl H m �.:ncnr Forcc 200 Lb Document generated by: C.d tmt ti 5 b - N'udncsAav lanum� Ib.201 B Force 2 Batch Part number Contatents Duration (.ti) 1% (Lb) 5% (Lb) Peak(Lb) 100119_07e552 N%'c t,xr,trc ;i3rdrLb 19120Lb 540201b, 100. M0118 075552 eo a J � t0 u O li 20 ea 9.02 oas aQG Cap Travel i(nj o,c 94i6 N McGuire Rd Post Falls,id 81,64 11'1 208-777-Ii495 (F4 NR-777-9527 (Ej Tant,a(rc fna-eps Corn 280 Rose St.Jerome,Id 81338 [P]208-324- 998 (Fj 208-124-5240 i I t ij Qw1m Comrof Depantirlit Tesler Name Tama Gan'01 TEST REPORT Edited FM kFPS LU Machine: il F\T1 IRIJ Test setup name 7,-q Fp,,22 1 1 2z Documtent generated by: Force 2 Batch Part number Comments Duration (s) 1% (Lb) $% (Lb) Peak(Lb) INV, 140 1 h IC0119 0757EE 60 '0 T J. 40 LL 20 20 0 Ole 004 0, 4114 016 Travei 1(in) 9456 N McGtwc Rd Posi Falls,ld 91954 it']20x--?77-84X5 IFJ 208-777-95.17 ILI I-anya(&,km-cps.cmn 290 Rose 51 Jertmr. Id 8331X fill 208-124-5999 fFI 20N-124-S240 0 � Quattt*Control nepartntenl Tester Nana Tanti t Garrett TEST REPORT Edited by FMI-FPS LI.( Machine: SI VNTt sIIll 21fwt Tew setup name.- t bmprescµm Tcm W;Z=1 1 2z Sct+,nr 71:xc it rn Sc r,.,�z fnrc.!rtit t!, Doctuttent getterated bl': t.tbi*ors t< 1c,h+r.Jn l.uiudr} tv 'utx Force 2 Batch errt4 Duvation (s) 1% (Lb) 5% (Lb) Peak(Lb) 10(11 tR RR 04)20 INS`a N-I(, 1 G'41 RHO I 75 IN t h 941 12111 h 100118 08:00.20 too- go- Go- 7 N 40 CA v 0 LL eo 0- et) - 0 UO2 004 ., _. 6e4 Travel 1(in) 9456 N McGuire Rd Post halli,Id 83934 fill 208-777-9485 fE)TanV-wafmt-cpsxom 290 Rose St Jerunr,Id.fi333S (PJ 208-324-5998 IF 2108-324-tt240 QuIla v Crnura!Npartnxnt Testcr Name Tama Garrot TEST REPORT Ethted by 1 F oll.rps t S t Machine: si rN roRlt 2;ott TeW setup name 22, �ett.�t,1istrl ii ttt Sarorattr Fur�c 2fH1 I-h Document generated by: l.ddort t 5 A hrdacsda;. -uua.tri n> 't:1�' Force 2 Batch Ptirt member Connnents Duration (s) 1% (Lb) 5% (Lb) teak (Lb) 10(11 19,.ON 42 29 MV c 1r4 41. r 1sq tl TG>r,0 f 1001is 080229 +oo ea 00 a J N as rU V S w zo- 1 a-t za t t 0 00. ono Travel 1(in) 9456 N MrGurre Rd P«o Faits.Id t+3954 1111 209-777-848; IF] )F.J Tanyaw tnu-eps.ertm 280 Rase St lertmr.Id 9333R [PI204-;24-;U9R IF]208-1,24-8240 �i Quale,Control Depanment Tesler Nan>< Tama Ciarrett TEST REPORT Edited bj-: FA11-$PS LLt Afachine: Test.Setup name: t unrrc,,wn_ et t UPS 22 1 i 2a un.��r tea,rt 1!au 4mnr I"nn�Ilni(h Document generated by: t.du,nt c � Nrdneutq t.xrun5 iu 10I� Farce 2 Batch Part number Comments Duration (s) 1 f (Lb) 5% (Lb) Peak(Lb) 100I IN nx 04.1e tvV 'rr-,F, 1 r,!n 220I1, "$6011, 42$60 th }op 100118 0904:46 8p Go- 7 J sa u O LL 20 O t0 V;.. Travel 1[in) or 9456 N McGuire Rd Post Falb, Id 83854 (P(208-777-8485 (F)208.777-952 (El Tanyarir fit*-eps.com 280 Rose St Jeror m:.[d_8.3338 (Pj 208-324-5998 (F1 208-124.9240 I s r 9 [ ( s i FMI-EPS QC Compression Testing Geofoam EPS 12 Job#:I Block#: 43D Date Expanded: 1/21/2016 Date Molded--Fl/22/2016 EPS-Minimum Density: 0 Date/Time Sampled: 1/11/2018 Tanya Garrett Sample# Weight Depth Width Height Reading at Reading at Volume 1 Density 1% 5% —(g) (in) I (i n) (in) 1% 5% (in') (lb/f3) 2.2 5.1 Psi/c /lb Job# Tester: Tanya Garrett Date Sampled: — January 11, 2018 Al 1,835 1.990 2.002 1.995 15.44 44.26 7.9480 0.88 3.88 11.11 A2 L878 L925 2.016 1.908 11.44 37.00 7.4046 0.9 953-6 2,95 12.669.891 A3 1.773 1.975 2.005 1,975 9.58 38.48 7,8208 0,86 2.42 9.72 11.28 A4 1.737 2.0001.9941 . 9.12 29,84 7,9920 0.83 2.29 1 7.48 10 1 2004 9.06 AS 1.725 2.003 1 1.913 1 2.000 10.34 1 35.36 7.6635T oa 1 2.76 L9,21:� 10.79I Avg L790 1,979 1.986 1.976 0.88 2.85 9.41 1034 Job# ester: Tanya Garrett Bate Sampled: January 11, 2018 131 B2 B3 B4 B 5 Avg Sid Dev o*, Density Jog# Tester: Tanya Garrett Date Sampled: January 11, 2018 C1 C2 C3 C4 C5 Sid Dev of Density Job# Tester: Tanya Garrett Date Sampled: January 11, 2018 D1 D2 D3 D4 D5 Std-Dev cal Density Tester: Tanya Garrett Date Sampled: January 11, 2018 rj E 1 E 2 E 3 E 4 E5 Avg td Dev ofpgpslty M FMI-EPS 9456 N. McGuire Rd Post Falls, ID 83854 1 IPJ (208) 777-8485 1 [F) (208) 777-9527 Page 1 FMI-EPS QC Flexural Strength Testing Geofoam EPS 12 Job#;I Block#: 43D )ate Expanded: 1/21/2016 Date Molded 11/22/2016 EPS Minimum Density: 0.7 Dat— e/Time Sampled: 1/11/2018 11:31 Tanya Garrett Sarnple# Weight Length Width Depth Flex Deflection Volume Density Flexural Support (g) {in} (in) (in} Reading {in'} i (lb/f') , Strength 10 Span (L) Job# Tester: — Tanya Garrett Date Sampled: January 11,2018 Al 8,525 12,000 2.463 0.995 6.18 1.6750 29,4082 1,10 38,0162 10 A2 8.366 12-000 2,890 1.020 5.81 1.6340 35-3736 O.90 28.9847 10 A3 8.681 12,000 2,900 1.001 6.05 1.6650 34-8348 0.95 31.2306 10 A4 10 AS la Avg 8,524 12.000 2.751 1,005 Std De I VW Oen L 12A'0156 0.98 32.74 Job# Tester: Tanya Garrett Date Sampled; January 11,2018 Bi B2 10 B3 10 B4 10 10 85 10 Avg Std DOvof Density, Job# Tester: Tanya Garrett Date Sampled: January 11,2018 Cl 10 C2 10 C 10 C4 10 C C5 10 itd Dev of density Job# Tester: Tanya Garrett Date Sampled: January 11,2018 D1 10 D2 10 D3 10 D4 10 DS 10 St�dDev of Density Job# Tester: Tanya Garrett Date Sampled: January 11,2018 El ---- 10 10 E 3 E4 10 10 10 Std,Dev of Density FMI-EPS 9456 N. McGuire Rd. Post Falls, ID 83854 [P] (208) 777-8485 IF] (208) 777-9527 Page 2 Duality Control 0epartmend Tester Name.Tanya Garrett TEST REPORT Edifed bY: FM1-EPS LLC' lfachine: STENTOR11 Stro,, Test setup name: C',mrp,ca>roa Tc�ENtiI' S"—T,mvf If m Spaar Parr 2u01 Document generated bt': t awor .,t,, Thurzdm fanuan.. I1.2018 Force 2 Batch Part number Comments Duration (s) 1% (Lb) 5% (Lb) Peak(Lb) it ill ly_I1 it tl, 1A1. A i W1I'll' 1,Jiu 11= +s gnu Lh 4x.2x0 It, 11,0118 1111:02 sa 4a D a a2a u a LL �a 0 ,a O aS a i a tS 02 Travel 1(in) 9456 N.McEntire Rd Post FaUs.id R3954.(P(208-777•8485 (FI 208-777-9527 Jt)Tanyaw fittfeps.com 280 Rose St,lerorm,id 83339 jPI 208-324-599R (F)208-324-8240 I I i Quality Control Departmend Tester Name Tanya Garrett TEST REPORT Edifeat by: Fktl-EPS LL(: Machine: $TFKi twn Jw) Test setup nante: Compm%swn_Test8PSl2 Srnew 1}avcl 11 rn Sens-F'ucc 2011 ti, Docttttte nt,*,rettet-ated bt': C.ddbrt r5 s Ttuusdaa luxuaw li,7t)ts Force s Batch Ptu•t Ntttabc'r ('t)ttttttetttc Duration(T) I o (Lb) 5% (Lb) Peak (Lb} tt-11t iN_li nx l5 iY-�`r.tc>t 1144011, 1-04111 4044111b 50 110118 11:08 15 40 30. J N 20 w v 0 LL to 0 to r.. a'y ..i al Travel 1(in] 9456 N-McGuire Rd.Post Fai6,Id. 83854-[P[208-777-8485 [FJ 208-777-9527 [E)Tanyaukft -eps_com 280 Rose St.Jerome,Id.83338 [P[208-324-5998-[F[208.324-8240 Quality Control Departmend Tester Name:Tanya Garrett TEST REPORT Edited by: F%it-EPs i,tc A?achine: S7l:-%TtrRrl s,ux, Test Set1t1J name: i�rFPSI? `rrra„r Tr�rd t!�n !x•n..+n F�ertt•�Ikt t.P+ Document generated bar: Cahtfln c5 k Thurada� lanutrr i,,20ix Force 2 Batch Purr t►umber Comments Duration(s) 1% (Lb) 5 0 (Lb) Peak (Lb) if UI ix tE 1220 iti 1'::tcat t SA-.x 4 sxf!I in 1S a%U tb 4::20 I+ �o 110116 111229 at, r 3 D I w 2p 0 W f �o U a Travel 1(in) of 94:ilb N' Nlc(hwe Rd Post Falb.ld,93854 (P[208-777-8485 [F[208-777.9527 [E[Tat►yatr_ifTweps.eom 280 Rose St.Jerome,Id.83338 (P['tl8-324-599$ (F(209-324-8240 Quality Control Departmend Tester Name;Tanya Garrett TEST REPORT Edited by: FMI-ties LLU Machine: 14ENTOR11;a,o TL, St Setup name: G0"grresswa,TarEPSl2 .,n5km Trmel I r rn $moor Fore,2wi Lt= Docurnentgenerated bp: calrton tlm'ujat tanuan II _'0#8 Force 2 Batch Pura number Comments Duration IA_I1 IiN IN♦,` (,r� I% (Lb) S% (Lb) Peak (Lb) !1 OI ntea� 1211 Lb 29 940 Lb 41)rp,rr 1 b ',0 11C1,78 11,1524 4Q 30 G J d 20 v O LL r0 0 it i �tS ..01 Travel t(in) 9456 N.McGuire Rd Post Falls,Id-83854 )P)208-777-8485.IF 12f}8-777.9527 )E)Tamra(wCm-cps,com 280 Rose St.Jerome.Id.83338-fill 209-324_5998-)F)208-324-8240 Quality Control Departmend Tester Name.Tanya Garrett TEST REPORT Edited k1,: FNI-EI-St_W Machine: S'rFI:T0R(150r* Test setup name: Compua,iun TmlFFSI, Scmur Travel I I n Sen„rc Furcc W Lh Doctr►rtent,reneratedki?: C'ahlorrO, - Thtn,day.►anr� U,Vlit Force 2 Batch Part r unther Comments Duration (s) 1% (Lb) 5% (Lb) Peak (Lb) IItot 19_I1 174; INN' test - 5r+6614 la 144,Lt, t4Imltb ;9t11101 h 11,01.18 11:17A5 40 35 30 2S a J 20 i N & C 15. LL tG- 5 0- 5- 0 002 004 GUG U68 Gs 012 Ora Ot& Travel 1(m) 9456 N.McGuire Rd.Post Falls,Id 83854 (P(208-777-8485 (F)208-777-9527 (EJ Tanyartifna-eps.com 280 Rose St Jerome.Id 83338 (P)208-324-5498 (F(208-324-8240 FMI f e EPS. Geofoam Gripper Plate (Friction Plate) Summary of In-House Testing Procedure and Report Materials Tested: 1) Two(2)Sheets EPS15 Geofoam manufactured in accordance with ASTM D6817,prepared to dimension of 1"x 5"x 5" 2) One(1) 22-gauge Gripper Plate Measurement Device 1) IMADA Digital Force Gauge Testing Equipment 1) Two(2)sheets%:"x S"x S"plywood 2) Cable to connect gripper plate to force gauge 3) Bench Vise 4) Motorized winch Testing Apparatus Setup 1) Attached the force gauge to the gripper plate 2) Place gripper plate between 2 sheets of EPS15 geofoam 3) Place foam sheets and gripper plates between 2 pieces of%2"x S"x 5" plywood 4) Place assembly into bench vise and clamp securely 5) Attach force gauge to motorized winch Testing Procedure 1) With test specimen securely fastened to the vise, retract the motorize winch and record maximum force at the point when the gripper plate slips,or the eps sheets slip,or the whole assembly slips from the vise and record the mode of slippage. Results of June 28, 2013 Mode of slippage: EPS slipped from Plywood Sheets Maximum Recorded Value:59.82 kilograms or 131.6 lbs Test is certified by Tony Bremer Follow-up Service Inspec:icn Report UL R18546118022810(13 36 INSPECTION Date 2018-02-28 1 File Number.; R18546 Responsible Office: nBuilding Volume: 1 Inspection Center: CCN: BRYX Product Type: terials& Systems UL Reo Name: Larry Shepherd Deliverable Type UL Rep ID: 52353 Party Site Number: 543880 Subscriber Factory No.: 100559-103 Manufacturer Name: FMI-EPS L L C Factory Rep Name Ms. tanya garrett Manufacturer Address: 9456 N MCOUIRE RD Factory Rep Phone: 208-777-8485 POST FALLS, ID 83854-6119 Factory Fep Email tanya@fmt-eps.com Nature of visit: Regular Inspection Sample Status: eTag Sample Selected UL Marks Used? Yes UL Marks Removed? No Variation Notice Issued? No Comments After Submission: — Model j Product Multiple Listed E—PS-1 5 1 lb Density BuLLLI�2� No DOCUMENTSSAMPLE If samples are required to be sent to ULI Laboratory, indicate below If required samples are not sent,explain in the Comments area. eTag Sample Additional Comments In addition to the requirements specified in the applicable UL Services agreement and Follow-Up Service Procedure UL tunher defines responsibilities. duties and requirements for both manufacturers and UL representatives in the document titled "UL Mark Surreiilance Requirements" that can be located at www_ut comlfus, and in accordance with the applicable terms and conditions of the document at ww gj,comtresponstbilih@s. Manufacturers without Internet access may obtain the current versions of these documents from their local UL customer service representative or UL field representative. i UL LLC 333 Pfingsten Road,Northbrook,IL 60062-2096 USA T:847.272.88001 F:847,272,8129 1 W:ul.com page r of r fR Vpt s Elastic Modulus, min., 5000 kPA (psi)' (730) / - - ---- Oxygen Index, min., " 24.0 i volume % j 1ASTM D1621 2 In addition to the requirements of ASTM D6817, geofoam blocks shall contain a flame- 3 retardant additive and shall have Underwriters Laboratories, Inc. (UL) Certification of 4 Classification as to External Fire Exposure and Surface Burning Characteristics. 5 Geofoam blocks should be considered combustible and/or subject to damage from 6 extreme heat; and should not be exposed to open flame or any source of ignition. 7 Geofoam blocks shall be treated to prevent insect attack and shall be protected from 8 vector intrusion. 9 10 Geofoam shall be manufactured using modified expanded polystyrene. 11 12 Manufacturer shall have a UL classification in category BRYX. U L 13 14 Each geofoam block shall be marked with the manufacturer's identification and type. 15 16 Hydrocarbon resistant geomembrane shall consist of reinforced or unreinforced tri- 17 polymer membrane manufactured from polyvinyl chloride, ethylene, interpolymer alloy, 18 and polyurethane, or a comparable polymer combination. Hydrocarbon resistant 19 geomembrane shall be capable of confining spilled liquid hydrocarbons, including 20 gasoline, diesel fuel, kerosene, hydraulic fluid. methanol, ethanol, mineral spirits, and 21 naptha. Hydrocarbon resistant geomembrane shall meet the requirements in Table 2: 22 23 TABLE 2: Physical Properties of Hydrocarbon Resistant Geomembrane Physical Property ASTM Designation Acceptance Value' Unleaded Gasoline Permeability D 814 „ 0.4 oz/ft2 Maximum per 24 f i hours I _.- Thickness I D 751 ° 28 mils Minimum Ir Grab Tensile 8 Strength (1"grip r D 751 ° 550 Ibf Minimum in each sample) i direction Elongation at Break I D 4632° 20 percent Minimum Toughness(Percent Elongation N/A _ 14,000 Ibf Minimum s {i x Grab Tensile Strength) i Bursting/Puncture Resistance f D 751 ° i ~M �� $00 Ibf Minimum (ball tip) } C Cold Crack Resistance (1"wide`11 D 2138° Pass at-30° F mandrel, 4 hours) Factory Produced Seams-, i D 751 ° i Bonded Width i 1.25" Minimum SR 99 ALASKAN WAY VIADUCT—REPLACEMENT SOUTH ACCESS—SR 99 CONNECTIONS 17A805 270 I and below the EPS geofoam blocks. 2 3 The unit Contract price per cubic yard for"Roadway Excavation Incl. Haul" shall include 4 the excavation, handling, and hauling of contaminated material. The cost of disposing 5 of contaminated material shall be included in "Disposing Contaminated Material". See 6 the Special Provision Removal of Structures and Obstructions for further information 7 on Contaminated Material, Contaminated Water, and Removal and Disposal of 8 Hazardous Material and Dangerous Waste. 9 10 "COS Mineral Aggregate Type 17", per ton. 11 12 "Structural Soil Mix", per cubic yard. 13 The unit Contract price per cubic yard for "Structural Soil Mix" shall be full pay for 14 performing the Work as specified and as shown in Plans. 15 16 "Force Account- Special Excavation", by force account as provided in Section 1-09.6. 17 To provide a common Proposal for all Bidders, the Contracting Agency has entered an 18 amount in the Bid Proposal to become a part of the Contractor's total Bid. 19 20 Section 2-03 is supplemented with the following: 21 22 ** **� 23 Materials 24 25 Materials for COS Mineral Aggregate Type 17 shall meet the requirements of the 26 subsection COS Mineral Aggregate Type 17 of the Special Provision Aggregates. 27 28 EPS Geofoam 29 The EPS geofoam blocks shall have the following minimum dimensions, plus or minus 30 0.5% in any direction: 31 32 Thickness 8 inches 33 Width 48 inches 34 Length 96 inches 35 36 Geofoam shall meet the requirements in Table 1. 37 38 TABLE 1: Physical Properties of EPS Geofoam TYPE ASTM D6817 i Property EPS22 Density, min., kg/m 3, 21.6 (Ib/ft3 ) (1.35) Compressive A50 Resistance (7.3) @ 1% deformation, ; min., kPa(psi) [Flexural Strength i 240 min., kPa (psi) (35.0) i SR 99 i ALASKAN WAY VIADUCT-REPLACEMENT SOUTH ACCESS-SR 99 CONNECTIONS 17A80S 269 i I 1 For the purpose of providing a common Proposal for all Bidders, the 2 Contracting Agency has entered an amount in the Bid Proposal for the item 3 "Handling, Hauling and Disposing Dangerous Waste" to become a part of the 4 total Bid by the Contractor. 5 6 Costs to handle and pay for water leaching from Engineer ordered stockpile 7 sites will be paid under the Bid item "Handling, Hauling and Disposing 8 Dangerous Waste", by force account. 9 10 Roadway Excavation and Embankment 11 12 Description 13 14 Section 2-03.1 is supplemented with the following: 15 16 17 For this project, all excavated material except asphalt, cement concrete pavement, and 18 pavement bricks shall be disposed of in accordance with the subsection Contaminated 19 Material of the Special Provision Removal of Structures and Obstructions. 20 21 The last paragraph of Section 2-03.1 is replaced with the following: 22 23 (******) 24 All Work described here must conform to the alignment, grades, or cross-sections 25 shown in the Plans, or as established by the Engineer. 26 27 Construction Requirements 28 29 Section 2-03.3 is supplemented with the following: 30 31 32 Excavation will not be allowed beyond limits shown in the Plans, City of Seattle 33 Standard Plans, or defined by the Specifications. 34 35 EPS Geofoam Lightweight Fill Construction S ,vQ OFF t oa _ c 36 Submittals 37 At least 30 calendar days prior to the start of Work requiring the geofoam blocks, 38 the Contractor shall submit the following to the Engineer for acceptance.- S"S'3o cy 40 1. A Plan sheet showing a profile and section view of the proposed r 41 embankment. The drawing shall clearly indicate the size, type, location i3_ I 42 and orientation of all new and salvaged geofoam blocks. 43 2. The location and methods for staged embankment construction and 44 protection. 45 3. The location and type of connectors. 5k91 � SQI.iHC g°►�9y,- Ml 00 46 4. Proposed ballasting or guying techniques. 47 5. Proposed placement methods. 5-M C7 48 6. Manufacturer's recommendations for handling, storing, cutting, and (3� 49 connecting the blocks. 50 51 Prior to the delivery of the EPS geofoam blocks, the Contractor shall furnish the 52 Engineer with a copy of manufacturer's test reports or a third party's certified test SR 99 ALASKAN WAY VIADUCT-REPLACEMENT SOUTH ACCESS-SR 99 CONNECTIONS 17ASD5 262 I report showing that the geofoam blocks meet the physical properties and standards 2 listed below in Table 1. 3 4 Acceptance 5 The Contractor shall submit to the Engineer a Manufacturer's Certificate of 6 Compliance for the first 100 cubic yards and for every 1500 cubic yards thereafter 7 before the geofoam is delivered to the site. 8 9 The Certificate of Compliance shall include current inspection reports showing that 10 the geofoam manufacturer is in compliance with a UL follow-up service program for 11 both flame and physical properties. In addition, computer generated stress-strain 12 data and the accompanying curves shall be produced from compressive testing 13 and supplied to the Engineer for acceptance. The curves and/or data shall clearly 14 indicate the stress at 1% strain and the modulus of elasticity. 15 16 The Contractor shall submit technical data, details, and test data for geofoam block 17 connectors. 18 19 If the material source changes during construction, the Contractor shall submit a 20 new Manufacturer's Certificate of Compliance. 21 22 Preconstruction Meeting 23 A preconstruction meeting shall be held at least five working days before the 24 Contractor begins Work. The meeting shall be at the site to discuss construction 25 procedures, personnel, and equipment, and other elements as specified herein. 26 27 Those attending shall include: 28 29 1. (representing the Contractor)The superintendent, on site supervisors, all 30 foreman, and inspection personnel. 31 2. (representing the Contracting Agency)The Engineer, key inspection 32 personnel, representatives from the WSDOT Construction Office, WSDOT 33 Materials Laboratory Geotechnical Division, and WSDOT Bridge and 34 Structures office. 35 36 If the Contractor's key personnel change, or if the Contractor proposes a significant 37 revision of the accepted submittal, an additional conference shall be held before 38 construction operations are performed. 39 40 Salvaged Geofoam 41 Test reports are not required when the Contractor reuses existing geofoam blocks 42 for landscape fill. 43 44 Protection and Storage 45 Geofoam blocks shall be handled and stored in accordance with the manufacturer's 46 recommendations. 47 48 Geofoam shall be protected from all petroleum-based solvents including but not limited 49 to gasoline and diesel fuel. 50 51 Blocks damaged during transit, handling, storage, or by the Contractor's operation 52 shall be replaced by the Contractor at no additional cost to the Contracting Agency. SR 99 ALASKAN WAY VIADUCT-REPLACEMENT SOUTH ACCESS-SR 99 CONNECTIONS 17A805 263 1 2 Construction Geotextile for soil separation shall meet the requirements in Section 9-33. 3 4 Sand Drainage Blanket shall meet the requirements of Section 9-03.13(1). 5 6 Additional EPS blocks used under landscaped areas shall meet the minimum 7 requirements in the following table: 8 TYPE ASTM Property = D6817 _-EPS12 Density. min. kg/m 3 11.2 ( Ib/�___.__ (0.70) CompressiveJ, 15 sistance (22) 1% deformation, min., kPa (psi) Flexural Strength T 69 ._. min., kPa (psi) (10.0) Elastic Modulus, min., 1550 kPA(psi)' (220) FOXYgE,n Index, min., 24.0 % _-_ .. - ............. . _.,.__. ._.._.__. ASTM D1621 10 Geofoam Tie Rods 11 Steel end plate shall conform to ASTM A 36 and shall be galvanized in accordance 12 with AASHTO M111. 13 14 All thread rods, and associated nuts and washers, shall conform to Section 9- 15 06.5(1), and shall be galvanized in accordance with AASHTO M 232. 16 17 Structural Soil 18 Structural soil mix shall consist of a uniform blend of Aggregate, Topsoil, Tackifier, and 19 Water. The following is an approximate ratio of materials for the structural soil mixture: 20 21 Amounts for 1 CY 22 Aggregate 21.45 Cubic Feet 23 Topsoil 24 8.25 Cubic Feet Tackifier 0.61 Pounds 25 Water As required 26 27 The actual ratio may vary and shall be adjusted in the field to ensure that there is 28 adequate topsoil to fill all voids in the aggregate stone mixture. SR 99 ALASKAN WAY VIADUCT-REPLACEMENT SOUTH ACCESS-SR 99 CONNECTIONS 17A805 272 t;�A-m C/MP)T- -F-5"77M,,l ) ,�'AWU( (::�«Lcv B S9iO o.j l yt6/cEt�� 1AJFCYta,q r.,, l USX 4c/2/A./G Zed,ti 20/S 'TJ , 0. 2dl �b c klss,'i VE-Q- �Ovc - t tm (t'if JJE.L Ss �=NCL. - F-�S rO-Am 4- $ )2 Y (EfS Z� vs Zo/.S -7,14t L r`car- , + f©, 2(D Ib Foams, atgs J - !Z. 'cy Fo�tn A-aLAJ rAJC-14 iZ4'SJQ I N b RgSdV �12-•cx3 $0,'Lo Foy n„ Rf ��y G`i Fin cosh es-, ��,� ©uLy �6G I GY Fait 6 I b Fob R9S1 . �`O �q_ 3S�GY �� FOPv,, �LSl� w rr 4 Esn A^ i*AA-r*ica A Aljl 'vim. it pvt - ZO l S, I to —j► zol6 T>uo6G3— fuse �A IRL I 4BOiz-)PnOFi T" $100 cy _ �95�cy nc GY 4- —V-(D LOAD t/m ANC UN REGYC.L. Feed Piz/ y q 5 R'� Z/v C`f FOA, D&- MWi Y1� 2,3c o G , v S"g Loans `/O c�r -� �£2 w�p LA23p2 + �G2Ji P �OsT --� T2itn,O So/tT- tom , DELI^a ., Usj",o OP(A►9T vL, �, S H/L � *70/Re- 2 Lp&at 3. O w2 iso 1frL sa "1rR.OGK �390 I .00 U-q5 CST Ntto Fe-O" Ptc.im,a.W f 38 Cy C..2EDrr r7 G y SA J i tiiE, L s3D F j LL- f 20�PA 2-1360 c y a fF Fawn 5 PrZcc�� Barry, Jason From: Smith, Susanne Provencio Sent: Friday, December 13, 2019 11:57 AM To: Barry, Jason Cc: Madfai, Mark Subject: RE: S. 228th GeoFoam Attachments: City_of_Kent_VE repo rt_24Ju115.pdf; The Columbian- Geofoam 10.13.13R.PDF; Ad Proof++SALMON CREEK_fmi-eps.pdf; Original Foam Limits Project Estimate 11-3-16.xlsx Hi Jason, We worked extensively with Joyce Lem at HDR and also with Lyle Stone and our Value Engineering team did some estimating for it as well. Info attached and as follows: ------------------------------------------------ From: Lem, Joyce <Joyce.Lem@hdrinc.com> Sent: Monday, May 2, 2016 4:44 PM To: Madfai, Mark<MMadfai@kentwa.gov>; Lyle Stone (GeoEngineers) <]stone@geoengineers.com> Cc: Walton, Randy<RWalton@kentwa.gov>; Smith, Susanne Provencio <SPSmith@kentwa.gov> Subject: RE: Salmon Creek/ 1-5 Interchange Project- (WSDOT Contract 8311) - Plans, Specs, Estimate Hi, everyone— 1. As a follow up to my 4/29 email below, attached are a PowerPoint file that contains photos of the Salmon Creek/ 1-5 Interchange project and two PDFs about the project (a Columbian newspaper article, the project flyer for FMI-EPS), all received from Steve Nelson. His contact info is below. I believe I've sent all of these previously to Mark, Randy and Lyle, but Susanne hasn't seen them. 2. I'd like to add that the drawings for the various geofoam walls for the Salmon Creek project (Volume 3 Plans) are challenging to follow. You have to focus on the Index of drawings at the front and wade through the Construction Staging drawings. I was hoping for an "easy" example at Walls W1 and W2, or Walls W7 and W8, which looked like they might be similar to our East Approach to the bridge. They're not. That's why I created the package of Wall W3 (goes with Walls W4, W12) for you. 3. For geofoam pricing, Lyle pointed out that the S 224th Street VE Study used $100 per CY for the geofoam. This fourth attachment (PDF) is PDF page 27 from that report. 4. Here's an email about geofoam pricing from Steve Nelson, the Geofoam vendor for FMI-EPS: (Sent 1/13/2016) Good Morning Joyce, Glad to provide you with photos and I will send some more, as I receive them from the plant. Thank you for the article on the Issaquah project and Brandon Cole's current employment. Did you get an opportunity to talk to him? Pricing in 2014, when oil was $100.00 per barrel, the price of EP5 Resin was $1.10 per pound plus freight to get it to our plant. Today Resin costs are currently $0.90 per pound plus freight. 5o for EP515 was about $8.00 more per CY in 2014 than it is right now. 1 EPS22 was about $12.00 more per CY in 2014 than it is right now. Resin Suppliers, BASF, Flint Hills and Nova are American Mfg.'s of EP5 Resin. We could buy cheaper bead from China, but our company will only buys American made products. Our Resin suppliers are saying the EPS Resin will move up and down in the $0.80 to $0.90 price range this year. The pricing (what I would quote a contactor) that I gave to you is FOB Kent, WA. It did not include the Contractors markup nor the labor to install it. Joyce, if you have any questions or need any other information please don't hesitate to contact me. Build A Great Day! A~ 67, �AFo� �)FlVl1-EPS,,E,; 3225 Eagleridge Way Bellingham, WA 98226 Ph: 206-550-3110 Email: steve@fmi-eps.com As noted in Steve's email, labor and General Contractor markup need to be added. As discussed previously, lighterweight geofoam costs less because uses less petroleum per volume. The lightest typical weight in roadway construction is EPS15, two levels lighter than the EPS22. I doubt that the Contractors will reduce the labor cost because the lighter geofoam should be easier to manhandle. So I think any savings would be due to lower material costs for the lighterweight EPS. GeoEngineers will need to run pavement type analyses to determine the required geofoam densities. At the top, I anticipate a layer of EPS22. It might be possible to use the lighterweight material one or more layers below that as the vertical loads are distributed laterally with depth. Joyce Lem, PE_,Sc ----------------------------- From: Barry,Jason <JBarry@kentwa.Pov> Sent: Friday, December 13, 2019 11:07 AM To: Smith, Susanne Provencio <SPSmith@kentwa.Pov> Subject: S. 228th GeoFoam Hi Susanne, Does the project have any foam material cost information we used back when deciding if and how much to use? Was there any supplier information on budgeting numbers? Thanks, Jason Barry, Capital Projects Manager Construction Management I Public Works Department KENT 220 Fourth Avenue South, Kent, WA 98032 Phone 253-856-5546 1 Cell 253-797-8462 2 VALUE ENGINEERING PROPOSAL CH-07 City of Kent S.224th Street Improvements Phase 1 and 2 Project Kent,WA TITLE: Reduce ground improvement by using lightweight fill to reduce fill loads DESIGN ELEMENT Markup BASELINE ASSUMPTION PROPOSED ALTERNATIVE Unit Cost Description % Unit Qty $ TOTAL $ Qty Unit Cost $ TOTAL $ Remove all ground 20% CY 20370 25.00 611,100 improvement Install geofoam in both east 20% CY 17333.3 100.00 2,080,000 and west embankments for walls higher than I Oft. (2/3 of 26,000 CY) Replace SEW embankment 20% CY 17333.3333 15.00 312,000 with foam Load distribution slab 20% CY 978 300.00 352,000 923,000 2,432,000 923,0001 1 2,432,000 CWE(BASELINE LESS PROPOSED) (1,509,000) M 24 of 118